TM 9-6115-668-135.49 SYNCHRONOUS GENERATOR SHOCK ABSORBERS MAINTENANCE.This task covers:a. Removalb. InstallationToolsEquipmentConditionsGeneral Mechanic’s Tool KitReference(item 2, appendix B)Generator Set 150 kW shutAutomotive Fuel and Electrical System Repair, Tool Kitdown,(item 3, appendix B)paragraph 2.5.2Materials/PartsPersonnel RequiredLoctite 243Twoitem 16, appendix E)Lubricant(item 6, appendix E)W A R N I N GDisconnect the negative battery cable first and then the positivebattery terminal cables. Failure to observe this warning could re-suit in severe personal injury or death.W A R N I N GEngine and generator shock mounts are not repairable. Do notattempt to disassemble. Failure to comply may cause injury ordeath.Do not stand in the operating area of the crane or forklift. Failureto observe these warnings could result in severe personal injuryor death.CAUTIONEngine should be lifted only far enough so that the engine mountcan be removed. Equipment will be damaged if the engine is liftedtoo high.Suitable spacing must be provided when engine shock absorbersare removed. Failure to provide proper support to the engine willcause damage to the equipment. The engine must be supported onthe engine mounts.5 - 2 2 0
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business