TM 9-6115-6685-13
4.15
UNlT HOOD-BASE FRAME GROUND STRAP MAINTENANCE.
This task covers:
a. Removal
b. Installation
INITAL SETUP
Tools
Equipment Conditions
General Mechanics Tool Kit
(item 2, appendix B)
Automotive Fuel and Electrical System Repair, Tool Kit
(item 3, appendix B
Reference
Generator Set 150 kW shut
down, paragraph 2.5.2
REMOVAL
Note the removal sequence of attaching hardware for installation to
ensure proper grounding. Failure to observe this warning could re-
suit in severe personal injury or death.
1.
Open flap (2, figure 4-26).
2.
Remove screw (3), serrated lock washers (4,8), washers (5,7), and grounding strap (6) from unit
hood assembly (1).
3.
Remove nut (9). serrated lock washer (10), washers (11, 12), and grounding strap (6) from screw
(13).
INSTALLATION
1.
Install serrated lock washer (10), washers (11,12), grounding strap (6) and nut (9) onto screw (13).
2.
Install serrated lock washers (4,8), washers (5.7) and grounding strap (6) on screw (3) and thread
screw (3) into unit hood assembly (1).
3. Close flap (2).
4-48