ARMY TM 9-6115-604-12NAVY NAVFAC P-8-633-12STEP 7.SET GEN/BUS VOLTMETER SWITCH TO GEN 2-3, THEN GEN 1-2, VERIFY THAT AC KILOVOLTSREADING IS THE SAME AT ALL THREE SETTINGS.STEP 8.SET PARALLEL SWITCH TO SINGLE SET. SINGLE SET INDICATOR WILL LIGHT.STEP 9.SET BREAKER CONTROL SWITCH TO CLOSE CLOSED INDICATOR WILL LIGHT.STEP 10. PERIODICALLY (NOT LESS THAN ONCE PER HOUR) MONITOR ENGINE AND GENERATORINDICATORS TO ENSURE CONTINUED OPERATION.STEP 11. PERFORM 'DURING OPERATION" PREVENTIVE CHECKS AND SERVICES AS SPECIFIED IN Table 3-2.STEP 12. TO STOP UNIT REFER TO Figure 2-23.Figure 2-22. Single Unit Remote Operation (Sheet 2 of 2)STEP 1SET BREAKERCONTROL SWITCH TO TRIP. OPEN INDICATOR WILL LIGHTSTEP 2ALLOW ENGINE TO OPERATE 5 MINUTES AT NO LOADSTEP 3SETMASTERSWITCH TO STOP.STEP 4SET MAINTENANCELOCKOUTSWITCH TO MAINTENANCE THIS SWITCH IS ON CABINET C IN THECONTROL ROOM OF GENERATOR SETSTEP 5SET 24v, DC CONTROL POWER CIRCUIT BREAKER TO OFF THIS BREAKER IS ON CABINET C IN THECONTROL ROOM OF THE GENERATOR SET.Figure 2-23. Stopping Generator Set - Single Unit Operation with Remote Control Module2-43