ARMY TM 9-6115-604-12
NAVY NAVFAC P-8-633-12
STEP 7.
SET GEN/BUS VOLTMETER SWITCH TO GEN 2-3, THEN GEN 1-2, VERIFY THAT AC KILOVOLTS
READING IS THE SAME AT ALL THREE SETTINGS.
STEP 8.
SET PARALLEL SWITCH TO SINGLE SET. SINGLE SET INDICATOR WILL LIGHT.
STEP 9.
SET BREAKER CONTROL SWITCH TO CLOSE CLOSED INDICATOR WILL LIGHT.
STEP 10. PERIODICALLY (NOT LESS THAN ONCE PER HOUR) MONITOR ENGINE AND GENERATOR
INDICATORS TO ENSURE CONTINUED OPERATION.
STEP 11. PERFORM 'DURING OPERATION" PREVENTIVE CHECKS AND SERVICES AS SPECIFIED IN Table 3-2.
STEP 12. TO STOP UNIT REFER TO Figure 2-23.
Figure 2-22. Single Unit Remote Operation (Sheet 2 of 2)
STEP 1
SET BREAKER CONTROL SWITCH TO TRIP. OPEN INDICATOR WILL LIGHT
STEP 2
ALLOW ENGINE TO OPERATE 5 MINUTES AT NO LOAD
STEP 3
SET MASTER SWITCH TO STOP.
STEP 4
SET MAINTENANCE LOCKOUT SWITCH TO MAINTENANCE THIS SWITCH IS ON CABINET C IN THE
CONTROL ROOM OF GENERATOR SET
STEP 5
SET 24v, DC CONTROL POWER CIRCUIT BREAKER TO OFF THIS BREAKER IS ON CABINET C IN THE
CONTROL ROOM OF THE GENERATOR SET.
Figure 2-23. Stopping Generator Set - Single Unit Operation with Remote Control Module
2-43