ARMY TM 9-6115-604-12
NAVY NAVFC P-8-633-12
CAUTION
PRIOR TO REMOVAL OF GENERATOR SET(S) FRO M
PARALLEL
OPERATION, MAKE SURE LOAD DOES NOT EXCEED FULL LOAD RATING
OF GENERATOR SET(S) REMAINING ONLINE. SEVERE DAMAGE TO
EQUIPMENT MAY RESULT FROM FAILURE TO MEET THIS CAU TION.
STEP 1. REDUCE LOAD UNTIL AC KILOWATTS METER INDICATES 60 KW OR LESS.
STEP 2. OUTGOING SET: SET BREAKER CONTROL SWITCH TO TRIP. OPEN INDICATOR WILL LIGHT.
STEP 3. OUTGOING SET: ALLOW ENGINE TO OPERATE 5 MINUTES AT NO LOAD.
STEP 4. OUTGOING SET: SET MASTER SWITCH TO STOP.
STEP 5. OUTGOING SET: SET MAINTENANCE LOCKOUT SWITCH TO MAINTENANCE.
STEP 6. 24v, DC CONTROL POWER CIRCUIT BREAKER TO OFF.
STEP 7. TO STOP ON-LINE SET REFER TO FIGURE 2-15.
Figure 2-21. Remote Control Panel, Controls and Instruments
2-38