ARMY TM 9-6115-604-12NAVY NAVFC P-8-633-12CAUTIONPRIOR TO REMOVAL OF GENERATOR SET(S) FRO MPARALLELOPERATION, MAKE SURE LOAD DOES NOT EXCEED FULL LOAD RATINGOF GENERATOR SET(S) REMAINING ONLINE. SEVERE DAMAGE TOEQUIPMENT MAY RESULT FROM FAILURE TO MEET THIS CAU TION.STEP 1. REDUCE LOAD UNTIL ACKILOWATTSMETER INDICATES 60 KW OR LESS.STEP 2. OUTGOING SET: SET BREAKERCONTROLSWITCH TO TRIP.OPEN INDICATOR WILL LIGHT.STEP 3. OUTGOING SET: ALLOW ENGINE TO OPERATE 5 MINUTES AT NO LOAD.STEP 4. OUTGOING SET: SET MASTERSWITCHTO STOP.STEP 5. OUTGOING SET: SET MAINTENANCELOCKOUTSWITCH TO MAINTENANCE.STEP 6. 24v, DC CONTROL POWER CIRCUIT BREAKER TO OFF.STEP 7. TO STOP ON-LINE SET REFER TO FIGURE 2-15.Figure 2-21. Remote Control Panel, Controls and Instruments2-38