ARMY TM 9-6115-604-12NAVY NAVFC P-8-633-12STEP 6.ON-LINE SET ADJUST VOLTADJ RHEOSTAT FOR AN ACKILOVOLTS READING OF 4 16KILOVOLTS (FOR 60 HERTZ OPERATION) OR 3 8 KILOVOLTS (FOR 50 HERTZ OPERATION).STEP 7.ON-LINE SET: SET GEN/BUSVOLTMETER SWITCH TO GEN2-3, THEN GEN 1-2 VERIFY THAT ACKILOVOLTSREADING IS THE SAME AT ALL THREE SETTINGS.STEP 8.ON-LINE SET: SET PARALLELSWITCH TO SINGLESET. SINGLESET INDICATOR WILL LIGHT.STEP 9.ON-LINE SET: SET BREAKERCONTROL SWITCH TO CLOSE CLOSED INDICATOR WILL LIGHT.STEP 10.ON-LINE SET: SET PARALLELSWITCH TO PARALLEL. PARALLEL INDICATOR WILL LIGHT.STEP 11.START ONE INCOMING GENERATOR SET (REFER TO Figure 2-13).STEP 12.INCOMING SET: ADJUST FREQADJ RHEOSTAT FOR A FRFOUENCY METER READING OF 50HERTZ OR 60 HERTZ, AS APPLICABLE.STEP 13.INCOMING SET: SET GEN/BUSVOLTMETER SWITCH TO GEN 3-1.STEP 14.INCOMING SET ADJUST VOLTADJ RHEOSTAT FOR AN ACKILOVOLTS READING OF 4.16KILOVOLTS (FOR 60 HERTZ OPERATION) OR 3 8 KILOVOLTS (FOR 50 HERTZ OPERATION).STEP 15.INCOMING SET. SET GEN/BUSVOLTMETER SWITCH TO GEN2-3, THEN GEN1-2 VERIFY THATACKILOVOLTSREADING IS THE SAME AT ALL THREE SETTINGS.STEP 16.INCOMING SET CHECK PHASE SEQUENCE USING PHASESEQ.SEL.SW AND 1-2-3 AND 3-2-1INDICATOR LIGHTS ENSURE THAT SETS ARE IN PHASE BEFORE PROCEEDING.STEP 17.INCOMING SET: SET PARALLELSWITCH TO PARALLEL. PARALLEL INDICATOR WILL LIGHT.STEP 18.INCOMING SET: SETSYNCHROSCOPE SWITCH TO ON. SYNCHROSCOPE WILL BEGINROTATING AND SYNCHRONIZING LIGHTS WILL BEGIN BLINKING.STEP 19.INCOMING SET: ADJUST FREQADJ RHEOSTAT UNTIL SYNCHRONIZING LIGHTS ARE BLINKINGVERY SLOWLY AND SYNCHROSCOPE NEEDLE IS ROTATING SLOWLY IN THE CLOCKWISE(FAST) DIRCTION.STEP 20.INCOMING SET: ADJUST VOLTADJ RHEOSTAT USING GEN/BUSVOLTMETER SWITCH AND ACKILOVOLTSMETER UNTILGENAND BUSVOLTAGES ARE IDENTICAL..STEP 21.INCOMING SET: WHEN SYNCHRONIZINGLIGHTS ARE DARK AND SYNCHROSCOPE NEEDLE ISIN 12 O'CLOCK POSITION, SET BREAKERCONTROL SWITCH TO CLOSE.CLOSED INDICATORWILL LIGHT.STEP 22.INCOMING SET: SETSYNCHROSCOPE SWITCH TO OFF.STEP 23.ALL SETS ADJUST VOLTADJ AND FREQADJ RHEOSTATS TO BALANCE THE LOAD ON ALLSETS AS INDICATED BY THE KILOVARS AND ACKILOWATTS. METERS ADJUST VOLTADJ TOEFFECT KILOVARS. ADJUST FREQADJ TO EFFECT KILOWATTS.STEP 24.IF ADDITIONAL GENERATOR SETS ARE TO BE PARALLELED, REPEAT STEP 11 THROUGH STEP23, ABOVE. FOR EACH SET.STEP 25.ALL SETS: PERIODICALLY (NOT LESS THAN ONCE PER HOUR) MONITOR ENGINE ANDGENERATOR INDICATORS TO ENSURE CONTINUED OPERATION.STEP 26.ALL SETS: PERFORM *DURING OPERATION" PREVENTIVE MAINTENANCE CHECKS ANDSERVICES AS SPECIFIED IN Table 3-2.STEP 27.TO STOP UNIT REFER TO Figure 2-20.Figure 2-19. Isochronous Parallel Operation (Sheet 2 of 2)2-37
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business