ARMY TM 9-6115-604-12NAVY NAVFC P-8-633-12STEP 6.ON-LINE SET: SET GEN/BUSVOLTMETER SWITCH TO GEN 3-1.STEP 7.ON-LINE SET: ADJUST VOLTADJ RHEOSTAT FOR AN ACKILOVOLTS READING OF 4 16KILOVOLTS (FOR 60 HERTZ OPERATION) OR 3 8 KILOVOLTS (FOR 50 HERTZ OPERATION).STEP 8.ON-LINE SET: SET GEN/BUSVOLTMETER SWITCH TO GEN2-3, THEN GEN1-2. VERIFY THATACKILOVOLTSREADING IS THE SAME AT ALL THREE SETTINGS.STEP 9.ON-LINE SET: SETPARALLELSWITCH TO SINGLESET. SINGLESET INDICATOR WILL LIGHT.STEP 10.ON-LINE SET: SET BREAKERCONTROL SWITCH TO CLOSE. CLOSE INDICATOR WILL LIGHT.STEP 11.ON-LINE SET: SET PARALLELSWITCH TOPARALLEL. PARALLEL INDICATOR WILL LIGHT.STEP 12.START ONE INCOMING GENERATOR SET (REFER TO Figure 2-13).STEP 13.INCOMING SET ADJUST FREQADJ RHEOSTAT FOR A FREQUENCY METER READING OF 50HERTZ OR 60 HERTZ, AS APPLICABLE.STEP 14.INCOMING SET: SET GEN/BUSVOLTMETER SWITCH TO GEN3-1.STEP 15.INCOMING SET ADJUST VOLTADJ RHEOSTAT FOR AN ACKILOVOLTS READING OF 4 16KILOVOLTS (FOR 60 HERTZ OPERATION) OR 3 8 KILOVOLTS (FOR 50 HERTZ OPERATION).STEP 16.INCOMING SET: SET GEN/BUSVOLTMETER SWITCH TO GEN2-3, THEN GEN1-2.VERIFY THATACKILOVOLTSREADING IS THE SAME AT ALL THREE SETTINGS.STEP 17.INCOMING SET: CHECK PHASE SEQUENCE USING PHASESEQ.SEL.SW. AND 1-2-3 AND 3-2-1INDICATOR LIGHTS. ENSURE THAT SETS ARE IN PHASE BEFORE PROCEEDINGSTEP 18.INCOMING SET: SET PARALLELSWITCH TO PARALLEL. PARALLEL INDICATOR WILL LIGHT.STEP 19.INCOMING SET: SET SYNCHROSCOPE SWITCH TO ON. SYNCHROSCOPE WILL BEGINROTATING AND SYNCHRONIZINGLIGHTS WILL BEGIN BLINKING.STEP 20.INCOMING SET: ADJUST FREQADJ RHEOSTAT UNTIL SYNCHRONIZINGLIGHTS ARE BLINKINGVERY SLOWLY AND SYNCHROSCOPE NEEDLE IS ROTATING SLOWLY IN THE CLOCKWISE(FAST DIRECTION.STEP 21.INCOMING SET: ADJUST VOLTADJ RHEOSTAT USING GEN/BUSVOLTMETER SWITCH AND ACKILOVOLTSMETER UNTIL GENAND BUSVOLTAGES ARE IDENTICAL.STEP 22.INCOMING SET: WHEN SYNCHRONIZINGLIGHTS ARE DARK AND SYNCHROSCOPE NEEDLE ISIN 12 O'CLOCK POSITION, SET BREAKERCONTROL SWITCH TO CLOSE. CLOSED INDICATORWILL LIGHT.STEP 23.INCOMING SET: SET SYNCHROSCOPE SWITCH TO OFF.STEP 24.ALL SETS: ADJUST VOLTADJ AND FREQADJ RHEOSTATS TO BALANCE THE LOAD ON ALLSETS AS INDICATED BY THE KILOVARS AND AC KILOWATTS METERS. ADJUST VOLTADJ TOEFFECT KILOVARS. ADJUST FREOADJ TO EFFECT KILOWATTS.STEP 25.IF ADDITIONAL GENERATOR SETS ARE TO BE PARALLELED, REPEAT STEP 12 THROUGH STEP24, ABOVE, FOR EACH SET.STEP 26.ALL SETS: ISOCHRONOUS WILL PICK UP LOAD CHANGES BEFORE BASE UNIT LOAD CHANGESWILL AFFECT VOLTAGE AND FREQUENCY OF DROOP-PARALLELED SETS EQUALLY. TO VARYFREQUENCY OR VOLTAGE OUT- PUT OF DROOP-PARALLELED SETS, ADJUST FREQADJ ORVOLTADJRHEOSTAT THE SAME WAY (INCREASE OR DECREASE) ON BOTH SETS.STEP 27.ALL SETS: PERIODICALLY (NOT LESS THAN ONCE PER HOUR) MONITOR ENGINE ANDGENERATOR INDICATORS TO ENSURE CONTINUED OPERATION.STEP 28.ALL SETS: PERFORM DURING OPERATION" PREVENTIVE MAINTENANCE CHECKS ANDSERVICES AS SPECIFIED IN Table 3-2.STEP 29.TO STOP UNIT REFER TO Figure 2-20.Figure 2-16. Droop Parallel Operation (Sheet 2 of 2)2-33
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business