ARMY TM 9-6115-604-12NAVY NAVFC P-8-633-122-6. PARALLELING THE GENERATOR SET (UNITS IN PARALLEL).NOTEThese procedures assume that one generator set Is on-line (connected to thedistribution feeder lines through switchgear). The set that Is to be paralleled shallbe designated the "incoming set"Refer to Figure 2-16 through Figure 2-19 for parallel operation, and to Figure 2-20 for removing a generator set fromparallel operationWhen operated In parallel, generator sets must have the same output voltage, frequency, phase relation, and phasesequence before they can be connected to a common distribution bus. Severe damage may occur to the generator setsif these requirements are not met Adjusting engine speed of the Incoming set while observing output frequency, theSYNCHRONIZING LIGHTS, and the SYNCHROSCOPE will bring the phase and frequency into exact agreement. Asthe phase and frequency approach the same value, the SYNCHRONIZING LIGHTS will gradually turn on and off. Whenthe blinking slows to a rate of once or less per second, close the main circuit breaker of the incoming set while theSYNCHRONIZING LIGHTS are at a point of being dark and the SYNCHROSCOPE is in the 12 o'clock position. Phasesequence has to do with the order in which the generator windings are connected If phase sequence Is not correct, theSYNCHRONIZING LIGHTS will not blink on and off together.CAUTIONShould either generator set lose speed, "buck", or "shudder" when theincoming set is connected to the distribution feeder lines, immediately setBREAKER CONTROL switch of incoming set to TRIP and recheck parallelingset-up procedures.When the Incoming set is first connected to the load (through appropriate switchgear) the following may occur if thephase. sequence, voltage, frequency, phase and engine performance are the same, the changeover will be smooth withonly the slightest hesitation In engine speed, if each output is slightly out of phase, one of the engines will "shudder" atthe point of changeover; if the phase sequence or voltage levels are Incorrect, the reverse power relay will trip on one ofthe generator sets and open its main circuit breaker contactors, if the Incoming generator set loses speed significantly oralmost stalls, the Incoming engine governing system may be defective.2-7. EMERGENCY STOPPING.a.To stop the generator set from the control room In an emergency, press the EMERGENCY SHUTDOWNpushbutton S7 on engine control cabinet C (3, Figure 2-1).b.To stop the generator set from outside the housing In an emergency, pull out the EMERGENCY SHUTDOWNcontrol In the skid base (Figure 1-1)c.To stop the generator set from the remote control module In an emergency, press the EMERGENCY SHUTDOWNpushbutton S7R (17, Figure 2-21)d.After stopping generator set In accordance with step a or step c, above reset the two air control valves Inaccordance with Figure 3-21.e.After stopping generator set In accordance with step b, above, reset EMERGENCY SHUTDOWN control In skidbase (Figure 1-1).2-31
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business