Table 2-13. Remote Control Panels, Controls and Instruments (Continued)
Figure 2-21, 5
FREQUENCY meter M103R
Indicates frequency of generator set out
50 or 60 Hz
put.
Figure 2-21, 6
SYNCHRONIZING LIGHTS
Used when paralleling to bring an in-
Both lights dark.
DS110R and DS111 R
coming unit on-line In phase.
Figure 2-21, 7
SYNCHROSCOPE M106R
Used with SYNCHRONIZING LIGHTS
--
DS11 OR and DS111 R when paralleling.
When the SYNCHROSCOPE pointer is
at the 12 o'clock position, DS110OR and
DS111R will be dark. Shows phase rela-
tionship between on-line and Incoming
units.
Figure 2-21, 8
AC KILOWATTS meter M107R
Indicates kilowatt output of generator
50 Hz - 625
set.
60 Hz - 750
Figure 2-21, 9
POWER FACTOR meter
Indicates power factor of generator set
50 Hz - 0.8
M104R
output LAG indicates an Inductive load
60 Hz - 0.8
LEAD indicates a capacitive load.
Figure 2-21, 10
LOW OIL PRESSURE indicator When lit, indicates engine has insuffi-
Dark
light DS2R
cient oil pressure.
Figure 2-21, 11
HIGH WATER TEMP Indicator
When lit, indicates engine has exces-
Dark
light DS3R
sively high coolant temperature.
Figure 2-21, 12
FAULT indicator light DS103R
When lit, Indicates generator set has a
Dark
fault condition.
Figure 2-21, 13
ANNUNCIATOR TEST
Used to test annunciator lights DS2R,
--
pushbutton S15R
DS3R, and DS103R and horn LS1R
Horn will sound and all annunciator
lights will light when button is pressed
Figure 2-21, 14
ALARM SILENCE pushbutton
Used to shut down horn LS1R and stop
--
S16R
flasher DS19 after an alarm circuit trips
Figure 2-21, 15
PARALLEL indicator DS35R and Indicates setting of PARALLEL SWITCH
--
SINGLE SET indicator DS36R
S6R.
Figure 2-21, 16
PARALLEL SWITCH S6R
Used to select PARALLEL or SINGLE
--
SET operation
Figure 2-21, 17
EMERGENCY SHUTDOWN
If pressed while operating, EMER-
--
pushbutton S7R
GENCY SHUTDOWN S7R will stop the
engine by cutting off air to the turbochar-
gers and deenergizing fuel solenoid
valve.
Figure 2-21, 18
SYNCHROSCOPE switch
Used to turn SYNCHROSCOPE M106
OFF
S115R
ON or OFF
Figure 2-21, 19
BREAKER CONTROL switch
Used to open and close load circuit
--
S4R
breaker CB101
Figure 2-21, 20
OPEN indicator DS33R and
Indicates whether load circuit breaker
--
CLOSED indicator DS34R
CB101 Is OPEN or CLOSED.