ARMY TM 9-6115-604-12
NAVY NAVFAC P-8-633-12
MAKE CERTAIN ALL SETS ARE SHUT DOWN AND THAT THERE ARE NO VOLTAGES AT
SWITCH GEAR TERMINALS BEING CONNECTED TO INCOMING SET. TAKE EXTREME CARE
NOT TO CROSS LO (NEUTRAL) WITH ANY OF THE OVER PHASES (L1, L2, OR L3). DEATH BY
ELECTROCUTION OR SEVERE EQUIPMENT DAMAGE MAY RESULT FROM FAILURE TO HEED
THIS WARNING.
NOTE
WHEN ENGINE TEMPERATURE IS BELOW 40°F (4°C) AND THE PREHEATER HAS NOT BEEN USED, ENGINE
ETHER PRIMER MAY BE REQUIRED TO USE EITHER PRIMER, THE GENERATOR SET MUST BE STARTED
FROM THE GENERATOR SET CONTROL ROOM WITH THE LOCAL REMOTE SW SET TO LOCAL. REFER TO
FIGURE 2-13.
STEP 1. CONNECT INCOMING SET AS SHOWN IN FIGURE 2-17.
STEP 2. INSTALL SHORTING PLUG ON ONE REACTIVE LOAD RECEPTACLE OF ON-LINE GENERATOR SET
AND EACH INCOMING GENERATOR SET REFER TO FIGURE 2-18.
Figure 2-24. Remote Droop Parallel Operation (Sheet 1 of 2)
2-44