ARMY TM 9-6115-604-12NAVY NAVFAC P-8-633-12STEP 3. ON-LINE SET SET MASTERSWITCH TO START AND RELEASE TO RUN. (THE ENGINE WILLAUTOMATICALLYCRANK FOR 15 SECONDS AND REST FOR 15 SECONDS UNTIL THE ENGINE HASSTARTED, FOR A TOTAL OF FOUR CRANK CYCLES ).STEP 4. ON-LINE SET ADJUST FREQADJ RHEOSTAT FOR A FREQUENCY METER READING OF 50 HERTZ OR60 HERTZ, AS APPLICABLE.STEP 5. ON-LINE SET SET GEN/BUSVOLTMETER SWITCH TO GEN3-1.STEP 6. ON-LINE SET ADJUST VOLTADJRHEOSTAT FOR AN AC KILOVOLTS READING OF 4 16 KILOVOLTS(FOR 60 HERTZ OPERATION) OR 3 8 KILOVOLTS (FOR 50 HERTZ OPERATION).STEP 7. ON-LINE SET- SET GEN/BUSVOLTMETERSWITCH TO GEN2-3, THEN GEN1-2. VERIFY THAT ACKILOVOLTSREADING IS THE SAME AT ALL THREE SETTINGS.STEP 8. ON-LINE SET SET PARALLELSWITCH TO SINGLESET. SINGLESET INDICATOR WILL LIGHT.STEP 9. ON-LINE SET SET BREAKERCONTROL SWITCH TO CLOSE.CLOSED INDICATOR WILL LIGHT.STEP 10. ON-LINE SET SET PARALLELSWITCH TO PARALLEL.PARALLELINDICATOR WILL LIGHT.STEP 11. INCOMING SET SET MASTERSWITCH TO START AND RELEASE TO RUN (THE ENGINE WILLAUTOMATICALLY CRANK FOR 15 SECONDS AND REST FOR 15 SECONDS UNTIL THE ENGINE HASSTARTED, FOR A TOTAL OF FOUR CRANK CYCLES )STEP 12. INCOMING SET ADJUST FREQADJ RHEOSTAT FOR A FREQUENCYMETER READING OF 50 HERTZOR 60 HERTZ, AS APPLICABLE.STEP 13. INCOMING SET: SET GEN/BUSVOLTMETERSWITCH TO GEN 3-1.STEP 14. INCOMING SET: ADJUST VOLTADJ RHEOSTAT FOR AN ACKILOVOLTS READING OF 4 16 KILOVOLTS(FOR 60 HERTZ OPERATION) OR 3 8 KILOVOLTS (FOR 50 HERTZ OPERATION).STEP 15 INCOMING SET: SET GEN/BUSVOLTMETERSWITCH TO GEN2-3, THEN GEN1-2. VERIFY THAT ACKILOVOLTS READING IS THE SAME AT ALL THREE SETTINGS.STEP 16. INCOMING SET: CHECK PHASE SEQUENCE USING PHASESEQ.SEL. SW AND 1-23AND 3-2-1INDICATOR LIGHTS. ENSURE THAT SETS ARE IN PHASE BEFORE PROCEEDING.STEP 17 INCOMING SET: SET PARALLELSWITCH TO PARALLEL.PARALLEL INDICATOR WILL LIGHT.STEP 18 INCOMING SET: SET SYNCHROSCOPESWITCH TO ONSYNCHROSCOPEWILL BEGIN ROTATING ANDSYNCHRONIZINGLIGHTS WILL BEGIN BLINKING.STEP 19. INCOMING SET ADJUST FREQADJ RHEOSTAT UNTIL SYNCHRONIZINGLIGHTS ARE BLINKING VERYSLOWLY AND SYNCHROSCOPE NEEDLE IS ROTATING SLOWLY IN THE CLOCKWISE (EST)DIRECTION.STEP 20 INCOMING SET: ADJUST VOLTADJ RHEOSTAT USING GEN/BUSVOLTMETERSWITCH AND ACKILOVOLTSMETER UNTIL GENAND BUSVOLTAGES ARE IDENTICAL.STEP 21 INCOMING SET: WHEN SYNCHRONIZINGLIGHTSARE DARK AND SYNCHROSCOPENEEDLE IS IN 12O'CLOCK POSITION, SET BREAKERCONTROLSWITCH TO CLOSE.CLOSEDINDICATOR WILL LIGHT.STEP 22 INCOMING SET SET SYNCHROSCOPE SWITCH TO OFF;STEP 23 ALL SETS ADJUST VOLTADJ AND FREQADJRHEOSTATS TO BALANCE THE LOAD ON ALL SETS ASINDICATED BY THE KILOVAR AND ACKILOWATTS METERS ADJUST VOLTADJ TO EFFECT KILOVARSADJUST FREQADJ TO EFFECT KILOWATTS.STEP 24 IF ADDITIONAL GENERATOR SETS ARE TO BE PARALLELED, REPEAT STEP 11 THROUGH STEP 24,ABOVE, FOR EACH SET.STEP 25 ALL SETS PERIODICALLY (NOT LESS THAN ONCE PER HOUR) MONITOR ENGINE AND GENERATORINDICATORS TO ENSURE CONTINUED OPERATION.STEP 26 ALL SETS PERFORM DURING OPERATION" PREVENTIVE MAINTENANCE CHECKS AND SERVICES ASSPECIFIED IN Table 3-2.STEP 27 TO STOP ENGINE REFER TO Figure 2-26.Figure 2-25. Remote Isochronous Parallel Operation (Sheet 2 of 2)2-47
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business