ARMY TM 9-6115-604-12NAVY NAVFAC P-8-633-12MAKE CERTAIN ALL SETS ARE SHUT DOWN AND THAT THERE ARE NO VOLTAGES ATSWITCH GEAR TERMINALS BEING CONNECTED TO INCOMING SET. TAKE EXTREME CARENOT TO CROSS LO (NEUTRAL) WITH ANY OF THE OTHER PHASES (L1, L2, OR L3). DEATH BYELECTROCUTION OR SEVERE EQUIPMENT DAMAGE MAT RESULT FROM FAILURE TO HEEDTHIS WARNING.WHEN ENGINE TEMPERATURE IS BELOW 40 F (4 C) AND THE PREHEATER HAS NOT BEEN USED, ENGINEETHER PRIMER MAY BE REQUIRED. TO USE ETHER PRIMER, THE GENERATOR SET MUST BE STARTEDFROM THE GENERATOR SET CONTROL ROOM WITH THE LOCAL REMOTE SW. SET TO LOCAL. REFER TOFIGURE 2-13.STEP 1.ALL SETS: REMOVE SHORTING PLUGS (REFER TO FIGURE 2-18). INTERCONNECT REACTIVELOAD COMPENSATION AND GOVERNOR CONTROL PARALLELING CABLES (REFER TO FIGURE 2-17) FOR ALL SETS TO BE PARALLELED.STEP 2SET FREQUENCYDROOP/ISOCHRONOUSSWITCH TO ISOCHRONOUS ON ON-LINE GENERATORSET AND EACH INCOMING GENERATOR SET. THIS SWITCH IS ON CABINET B IN THE CONTROLROOM OF EACH GENERATOR SET.Figure 2-25. Remote Isochronous Parallel Operation (Sheet 1 of 2)2-46