Table 4-1. Unit Preventive Maintenance Checks and Services (PMCS). CONT.
Table 4-2. Troubleshooting. - Continued

Power Plant An/Mjq-18 (Nsn 6115-00-033-1398) (2) Mep-003A 10Kw 60Hz Generator Sets M103A3 2-Wheel, 1-1/2 Ton Modified Trailer Page Navigation
  37    38    39    40    41  42  43    44    45    46    47  
img
. . . . . . .
ARMY TM 5-6115-633-14&P
4-14.
Power Plant Troubleshooting. Table 4-2 contains troubleshooting information for locating and
correcting operating troubles which may develop in components unique to the power pIant end item.
Each malfunction is followed by a list of tests or inspections which will help determine probable cause
and corrective actions to take. Perform the tests/inspections and corrective actions in the order
listed. This manual cannot list all malfunctions that may occur, nor all tests or inspections and
corrective actions. If a malfunction is not listed or cannot be corrected by listed corrective actions,
notify your supervisor.
Table 4-2. Troubleshooting.
Malfunction
Test or inspection
Corrective action
1. POWER IS ABSENT AT SWITCH BOX LOAD TERMINAL(S) WHEN ONE GENERATOR SET IS
OPERATING.
Check that generator set circuit breaker is set to ON position.
Step 1.
If circuit breaker is in OFF position, set to ON position.
Check for power output at generator set load terminals.
Step 2.
If power is absent at generator set load terminals, troubleshoot
generator set. (Refer to TM 5-6115-585-12).
Inspect power cable connections inside switch box for looseness or broken wire
Step 3.
terminals.
Tighten loose connections. If any wire terminals are broken, replace
cable (paragraph 4-25, d.) or refer to higher level of maintenance for
repair.
Perform continuity check on associated generator set power cable
Step 4.
(paragraph 4-23, a.).
If cable is defective, replace cable (paragraph 4-25, d.) or refer to
higher level of maintenance for repair.
Perform continuity check on rotary switch (paragraph 4-23, c.).
Step 5.
If switch is defective, notify higher level of maintenance.
2. POWER IS ABSENT AT ONE OR MORE SWITCH BOX LOAD TERMINALS WHEN EITHER GENERATOR
SET IS OPERATING.
Check wire associated with non-functioning load terminal(s) for looseness or
Step 1.
broken terminals inside switch box.
Tighten loose connection(s). If any terminals are broken, replace wire
(paragraph 4-25, c.).