TM 5-6115-593-34
NAVFAC P-8-631-34
TO-35C2-3-463-2
(b)
Connect the frequency meter to the
output terminals of the generator set.
(2)
Test.
(a)
Start and operate the set at rated
frequency and no load.
(b)
Close the switch (see figure 512.3.I)
and use resistance, R1 to adjust the
voltage to the overvoltage value
specified in table 16-1. The set has
provisions for shutdown upon an
overvoltage condition, it will be
necessary to temporarily deactivate
this provision to permit adjustment
of the overvoltage value. This may
be
done
by
activation
of
the
"protective
bypass"
(BATTLE
SHORT) switch. Do not deactivate
the circuit interrupter trip circuitry.
(c)
Open
the
switch,
reset
the
overvoltage circuit and adjust the
resistance,
R2,
until
voltmeter
number 2 reads rated voltage.
(d)
Repeat (b) and (c) to ensure that
the specified overvoltage and rated
voltage settings are correct.
(e)
Set the oscillograph chart speed
such that the individual waveform
peaks are clearly visible. Set the
timing lines to a minimum of 0.01
seconds per line or use a 60 Hz
time trace. Adjust the trace peak-
to-peak amplitude to a minimum of
one inch (or 25 millimeters).
(f)
Read and record both voltmeter
readings.
(g)
With the oscillograph recording and
the circuit interrupter closed, close
the switch. (See figure 512.3-I.)
(h)
Reactivate the shutdown provision if
used.
(i)
The generator set contains an
overvoltage malfunction indicator,
check and record its indication.
(j)
Record whether or not the set shuts
down.
(k)
Open
the
switch,
reset
the
overvoltage circuit if necessary,
restart the set if required, and close
the circuit interrupter.
(l)
Repeat steps (d) through (k) above
two additional times.
d.
Procedure II (Undervoltage).
(1)
Preparation for test.
(a)
Locate the input terminals of the
undervoltage sensing circuit and
connect the apparatus as illustrated
in figure 512.3-I.
(b)
Repeat step (b) of paragraph
16-20c(1)(b).
(2)
Test.
(a)
Start and operate the set at rated
frequency and no load.
(b)
Close the switch (see figure 512.3-I)
and use the resistance, R1 to adjust
the voltage to the rated value.
(c)
Open the switch and adjust the
resistance,
R2
until
voltmeter
number 2 reads the undervoltage
value specified in table 16-1. This
test shall be repeated for each
under
16-17