TM 5-6115-593-34NAVFAC P-8-631-34TO-35C2-3-463-2voltage connections if applicable.d.Results.(1)From the oscillograms taken in 16-18c(2)(d), determine the time between theindicated closure of the short-circuitingswitch and the opening of the circuitinterrupter. See figure 512.1-II.(2)Calculate the short-circuit current usingthe peak-to-peak amplitudes of thecurrent trace and the steadystateammeter reading prior to application ofthe short circuit. See figure 512.1-II.(3)Tabulate the above results and themalfunction indicator indication for eachline connection at each voltageconnection and compare the results withthe requirements in table 16-1.16-19. CIRCUITS INTERRUPTER TEST (OVERLOADCURRENT).a.General.A circuit interrupter is connectedbetween the generator voltage reconnectionsystem and the generator output terminals todisconnect the generator output from the loadand to protect the generator from sustainedoverload current. The circuit interrupter isoperated from a current sensor external to theinterrupter.b.Apparatus.Instrumentation for measuring loadconditions and field voltage and current shall beas described and illustrated in MIL-HDBK-705.In addition, a stopwatch or an oscillograph withgalvanometer matchingnetwork and anoninductive shunt as described and illustratedin MIL-HDBK-705. Method 106.1, paragraph106.1.3 and galvanometers having a flatfrequency respond (within plus or minus 5percent) from DC to 3,000 Hz.c.Procedure.(1)Preparation for Test. Connect the loadand field instrumentation in accordancewith the applicable figure of MIL-HDBK-705, Method 205.1, paragraph 205.1.10for one voltage and frequency.CAUTIONIf the circuit interrupter fails tooperate within the time specifiedin table 16-1 at any time duringthe performance of this method,manually open the circuitinterrupter and reduce the loadimpedance to rated value beforereclosing the circuit interrupter.Record on the data sheet thefailure of the interrupter tooperate and the total elapsed timethe overload was on the set.(2)Test.(a)Start and operate the generator setat rated voltage, rated frequency,and rated load.(b)Allow the generator set to stabilizeat rated load, voltage, andfrequency. During this period,readings of the load and fieldinstrumentation shall be recorded atminimum intervals of 10 minutes. Ifnecessary, adjustments to the load,voltage, and frequency may bemade to maintain rated load atrated voltage and frequency.Adjustments to the load, voltage, orfrequency shall be noted on thedata sheet. Stabilization will beconsidered to have occurred whenfour consecutive voltage andcurrent readings of the exciter fieldeither remain unchanged or haveonly minor variations about anequilibriumcondition with noevident continued increase ordecrease in value after the lastload, voltage, or frequencyadjustment has been made.16-15
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business