TM 5-6115-593-34NAVFAC P-8-631-34TO-35C2-3-463-216-17. OVERSPEED PROTECTIVE DEVICE TEST.a.General.Overspeeds will not be possible toobtain due to limiting factors incorporated in thefuel injection pump.b.OverspeedSwitch.Perform a bench test on theoverspeed switch to check the proper trip points.c.FunctionalCheck.Perform a function check ofthe circuit manually. Refer to AC-DCschematics.16-18. CIRCUIT INTERRUPTER TEST (Short Circuit).a.General.A circuit interrupter is connectedbetween the generator voltage reconnectionsystem and the generator set output terminals todisconnect the generator output from the loadand also to protect the generator from a shortcircuit. The circuit interrupter is operated from acurrent sensor external to the interrupter.b.Apparatus.Instrumentation for measuring loadconditions shall be as described and illustratedin MIL-HDBK-705. In addition, a noninductiveshunt; a short-circuiting switch; a galvanometermatching networks; as oscillograph as describedand illustrated in MIL-HDBK-705, Method 106.1,paragraph 106.1.3; and galvanometers having aflat frequency response (flat within plus or minusfive percent) from DC to 3,000 Hz will berequired.c.Procedure.(1)Preparation for the test.(a)Connect the load andinstrumentation in accordance withthe applicable figure of MIL-HDBK-705,Method 205.1, paragraph205.1.10 for one for one voltageand frequency.(b)Connect the shunt, galvanometermatching network, oscillograph, andshort-circuiting switch as illustratedin figure 512.1.1.(2)Test.(a)Start and operate the generator setat rated voltage, rated frequencyand rated load.(b)Set the oscillograph time marker toa minimum of 0.01 seconds or usea 60 Hz timing trace set the chartspeed such that the individual peaksof the current waveform are clearlyvisible and adjust the peak-to-peakrated current amplitude to aminimum of 0.5 inch (orapproximately 12 millimeters).(c)Prior to closing the short-circuitingswitch, record a portion of thesteady state load for calibration.With the same load conditionsrecord all instrument readings.(d)With oscillograph still recording thesteady state current, close the short-circuiting switch.CAUTIONIf the circuit interrupter fails tooperate within the specified time,remove the short circuit toprevent damage. Note the failureto operate on the data sheet.(e)The generator set contains a short-circuit malfunction indicator, checkand, record its indication.(f)Repeat steps (a) through (e) abovefor each possible short circuitcondition (L1-L0,L2-L3, L1-L2-L3 etc.)(g)Repeat steps (a) through (f) abovefor both16-14
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business