TM 5-6115-593-34NAVFAC P-8-631-34TO-35C2-3-463-2CAUTIONDo not exceed 125 percent ofrated load.(e)Hold the conditions in step (c)above for two minutes. However, ifthe voltage and frequency cannotbe maintained within 1 percent oftheir rated values, the load must beadjusted to the point at which thevoltage and frequency can bemaintained within 1 percent of theirrated values for two minutes.CAUTIONItmaybenecessarytoreducetheloadtoavaluebelowtheratedkilowatt load for a short period oftimetopreventseriousover-heatingor damage to thegeneratorset if the aboveconditions cannot be readilyattained. (Monitor instrumen-tation.)(f)During the two minute period recordall instrument readings includingthermal and pressure instrumenta-tion. (On 3-phase sets it is notnecessary to record line-to-linevoltages).(g)Reduce the load to rated kilowattload and allow the generator set tocool for 10 minutes.(h)Repeat steps (d) through (g) aboveuntil three valid sets of maximumpower data are obtained.16-22