B-BeforeTM 5-6115-584-12NAVFAC P-8-622-12TO-35C2-3456-1TM-05682C-12Table 3-2. Operator/Crew Preventive Maintenance Checks and Services (Cont.)NOTEWithin designated interval, these checks are to be performed in the order listed.D-DuringA-AfterW-WeeklyM-MonthlyItem To BeInspectedGenerator set(cont.)Controls anda. Batteryindicatorb. Frequencymeterc. Percent ratedcurrent meterd. Voltmetere. Oil pressuregagef. Fuel gageFuel tankProceduresCheck for and have repairedor adjusted as necessaryEquipment isNot Ready/Available if:c. Check that grounding cable is installed andtight (para 4-2e, fig. 4-2).d. Check restriction indicator; if RED, clean orreplace air filter element. (para 3-18)NOTEDuring starting and operation, check restrictionindicator. Check for leaks, loose or cracked parts,unusual noise, rough-running, excessive vibration,lack of power, incorrect instrument readings, orany indication of a failing or defective component.If suspected, notify organizational maintenance.Instruments will indicate within specified limits.Normal indication: yellow while charging, greenwhen fully charged.Normal indication: 60 Hz (red line) with loadon generator.Normal indication: Percent of load (output) oneach phase. Not to exceed 100% load or 5%difference between phases.Normal indication: 120, 208 or 240 voltsdepending on AMP Volt transfer switch position.Normal indication: 20 to 45 psig at rated RPM.Normal indication: FullFill tank upon completion of operation.Dangerous gases. Do not smoke or use open flamewhile servicing battery, due to possible presenceof hydrogen, a highly explosive gas.Cable is improperlyinstalled or missing.Air cleaner ismissing orunserviceable.Indicator indicatesred.Indicating inthe Red.Proper frequencycannot bemaintained.Desired voltagecannot be obtained.Oil pressure dropsbelow 15 psig.Change 63-5
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business