load equals a 100% meter reading for maximum rated
load. A 1.0 power factor load equals a 80% meter
reading for maximum rated load.
i. During operating of the Generator Set observe
the following.
(1) Check % rated current meter.
(2) Check fuel level gauge periodically.
(3) Oil pressure gauge located on engine should
indicate 20 psi minimum.
(4) Check running time meter periodically in
order to perform preventive maintenance check and
TM 5-6115-584-12
NAVFAC P-8-622-12
T O - 3 5 C 2 - 3 - 4 5 6 - 1
TM-05682C-12
(5) Battery indicator should indicate yellow while
battery is charging, green when battery is fully
charged.
(6) AC voltmeter should indicate 120V., 208V. or
240V. depending on load connection.
(7) Frequency meter should indicate 60 Hz (at
full rated load).
j. During operation, inspect for leaks, paying par-
ticular attention to engine fuel and oil lines and con-
services at proper intervals.
nections.
Figure 2-4. Load Terminal and Reconnection Configuration
2-5