A - PARALLEL OPERATION OF TACTICAL UTILITY GENERATOR SETS (LOAD SHARING)STEP 1.THE FIRST SET STARTED SHALL BE DESIGNATED AS “ON-LINE” AND THE SETS IN PAR-ALLEL OPERATION SHALL BE DESIGNATED “ON-COMING.” WITH ALL SETS SHUT DOWN CONNECTTHE LOAD TERMINAL BOARDS AS DESCRIBED IN FIGURE 2-3.CHECK THAT THE VOLTAGE RECON-NECTION BOARDS (FIGURE 2-4) OF THE SETS ARE IDENTICALLY POSITIONED.CAUTIONDO NOT PLACE THE CIRCUIT BREAKER SWITCH ON ANY OF THEGENERATOR SETS IN THE CLOSEPOSITION UNTIL SPECIFICAL-LY DIRECTED TO DO SO.CLOSING THE CIRCUIT BREAKERSWITCH AT ANY OTHER TIME MAY SEVERELY DAMAGE ONE ORMORE OF THE GENERATOR SETS.CAUTIONCHECK THAT THE MAIN POWER SWITCH (FIGURE 2-3.2) AT THELOAD IS OPEN BEFORE ATTEMPTING TO PLACE A GENERATOR SETON LINE.STEP 2.START THE GENERATOR SETS AS DESCRIBED IN FIGURES 2-6 AND 2-7.DO NOT PER-FORM STEP 8 OF FIGURE 2-7.STEP 3.HOLD THE CKTBRKSWITCH (FIGURE 2-5) OF THE “ON-LINE” SET IN THE CLOSEPO-SITION UNTIL THE CKTBRKINDICATOR LIGHT ILLUMINATES.PLACE THE OPERATION SWITCH INTHE PARALLEL POSITION.STEP 4.SET “VOLT-AMPS TRANSFER SWITCH” IN THE LI-LO POSITION.ADJUST THE VOLTAGEADJUST RHEOSTAT UNTIL THE AC VOLTMETER INDICATES 122 VOLTS FOR THE 120/208 CONNEC-TION AND 244 VOLTS FOR THE 240/416 CONNECTION.ADJUST MANUAL SPEED CONTROL UNTILTHE FREQUENCY METER INDICATES 61 HERTZ.PLACE THE OPERATION SWITCH OF THE “ON-COM-ING” SET IN THE PARALLELPOSITION.NOTEOBSERVE THE SYNCHRONIZING LIGHTS OF THE “ON-COMING” SET.THE LIGHTS SHOULD GO ON AND OFF SIMULTANEOUSLYIF THELIGHTS GO ON AND OFF ALTERNATELY, SETS ARE OUT OF PHASE.STOP BOTH SETS AND CORRECT INTERCONNECT CABLES (FIGURE2-3.1). IF PROBLEM PERSISTS, REFER TO NEXT HIGHER LEVELOF MAINTENANCE.STEP 5.ADJUST THE MANUAL SPEED CONTROL OF THE “ON-COMING” SET UNTIL THE SYNCHRON-IZING LIGHTS, SIMULTANEOUSLY, REMAIN ON OR OFF AT 2 TO 3 SECOND INTERVALS.STEP 6.CAREFULLY OBSERVE THE SYNCHRONIZING LIGHTS OF THE “ON-COMING” SET AND, ATTHE INSTANT BOTH LIGHTS GO DARK, PLACE THE CKTBRK SWITCH OF THE “ON-COMING” SET TOTHE CLOSEPOSITION.WHEN THE CKTBRK INDICATOR LIGHT ILLUMINATES, THE SETS ARE OP-ERATING IN PARALLEL.Figure 2-10A.Parallel Operation of Tactical Utility Generator Sets(Load Sharing and Load Transfer) (Sheet 2 of 4)Change 122-26.5
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business