A - PARALLEL OPERATION (LOAD SHARING)
STEP 1.
THE FIRST SET STARTED SHALL BE DESIGNATED AS ON-LINE AND THE SETS IN PAR-
ALLEL OPERATION SHALL BE DESIGNATED ON-COMING. WITH ALL SETS SHUT DOWN INSTALL
THE PARALLELING CABLE AND CONNECT THE LOAD TERMINAL BOARDS AS DESCRIBED IN FIGURE
2-3A.
CHECK THAT THE VOLTAGE RECONNECTION BOARDS (FIGURE 2-4) OF THE SETS
TICALLY POSITIONED.
CAUTION
DO NOT PLACE THE CIRCUIT BREAKER SWITCH ON ANY OF THE GEN-
ERATOR SETS IN THE CLOSE POSITION UNTIL SPECIFICALLY DI-
RECTED TO DO SO.
CLOSING THE CIRCUIT BREAKER SWITCH AT
ANY OTHER TIME MAY SEVERELY DAMAGE ONE OR MORE OF THE GEN-
ERATOR SETS.
CAUTION
CHECK THAT THE MAIN POWER SWITCH (FIGURE 2-3.2) AT THE LOAD
IS OPEN BEFORE ATTEMPTING TO PLACE A GENERATOR SET ON LINE.
STEP 2.
START THE GENERATOR SETS AS DESCRIBED IN FIGURES 2-6 AND 2-7. DO
FORM STEP 8 OF FIGURE 2-7.
ARE IDEN-
NOT PER-
STEP 3.
HOLD THE CKT BRK SWITCH (FIGURE 2-5) OF THE ON-LINE SET IN THE CLOSE PO-
SITION UNTIL THE CKT BRK INDICATOR LIGHT ILLUMINATES.
PLACE THE OPERATION SWITCH
IN THE PARALLEL POSITION.
STEP 4.
ADJUST THE VOLTAGE ON BOTH SETS TO THE REQUIRED VALUE.
ADJUST THE FREQUEN-
CY OF THE ON-LINE SET TO THE REQUIRED VALUE.
PLACE THE OPERATION SWITCH OF THE
ON-COMING SET IN THE PARALLEL POSITION.
NOTE
OBSERVE THE SYNCHRONIZING LIGHTS OF THE ON-COMING SET.
THE LIGHTS SHOULD GO ON AND OFF SIMULTANEOUSLY.
IF THE
LIGHTS GO ON AND OFF ALTERNATELY, SETS ARE OUT OF PHASE.
STOP BOTH SETS AND CORRECT INTERCONNECTION CABLES AS DE-
SCRIBED IN (FIGuRE 2-3.1).
IF THE PROBLEM PERSISTS, RE-
FER TO NEXT HIGHER LEVEL OF MAINTENANCE.
STEP 5.
ADJUST THE FREQUENCY OF THE ON-COMING SET A LITTLE HIGHER THAN THE ON-
LINE SET.
THEN REDUCE THE FREQUENCY SLOWLY WITH THE FREQUENCY ADJUST RHEOSTAT UN-
TIL THE SYNCHRONIZING LIGHTS REMAIN ON OR OFF AT 2 TO 3 SECOND INTERVALS.
STEP 6.
CAREFULLY OBSERVE THE SYNCHRONIZING LIGHTS OF THE ON-COMING SET AND, AT
THE INSTANT BOTH LIGHTS GO DARK, PLACE THE CKT BRK SWITCH OF THE ON-COMING SET TO
THE CLOSE POSITION.
WHEN THE CKT BRK INDICATOR LIGHT ILLUMINATES, THE SETS ARE OP-
ERATING IN PARALLEL.
Figure 2-10. Parallel Operation (Load Sharing and Load Transfer) (Sheet 2 of 5)