CAUTIONTHE KILOWATT METER AND AC AMMETER INDICATE PERCENTAGES ANDDONOTINDICATE TRUE KW AND AMPERE READINGS.STEP 7.WITH NO EXTERNAL LOAD ON THE PARALLELED SETS, ADJUST THE FREQUENCY ADJUSTRHEOSTAT OF THE “ON-COMING” SET UNTIL BOTH RATED LOAD METERS (KILOWATT) READ ZERO.ADJUST THE VOLTAGE ADJUST RHEOSTAT OF THE“ON-COMING SET UNTIL THE PERCENT OF RATEDCURRENT METERS (AMMETERS) ON BOTH SETS READ ZERO.TURNING COUNTERCLOCKWISE WILL DE-CREASE READINGS.STEP 8.APPLY LOAD TO THE SETS.THE KILOWATT LOAD SHOULD DIVIDE SO THAT THE LOADON EACH SET IS EQUAL.IF THE LOAD AND CURRENT ARE NOT SHARED EQUALLY, ADJUST THEVOLTAGE AND FREQUENCY RHEOSTATS OF THE “ON-COMING” SET UNTIL LOAD AND CURRENT AREDIVIDED EQUALLY BETWEEN THE GENERATOR SETS.STEP 9.THE CURRENT SHOULD DIVIDE SO THAT THE OBSERVED DIFFERENCE BETWEEN THE CUR-RENT ON ANY PHASE BETWEEN THE “ON-LINE” AND “ON-COMING” SETS IS NOT MORE THAN 20PERCENT. IFSTEP 10. TOTHE READINGS ARE NOT WITHIN 20 PERCENT, NOTIFY HIGHER LEVEL MAINTENANCE.NOTEIF THE REVERSE POWER INDICATOR OF EITHER SET ILLUMINATESAND THE MAIN LOAD CONTACTOR OPENS, OPEN THE MAIN POWERSWITCH AND REPARALLEL THE GENERATOR SETS.CAUTIONWHEN GENERATOR SETS ARE BEING OPERATED IN PARALLEL, ONE ORMORE OPERATORS MUST REMAIN WITH THE SETS TO MONITOR THE RAT-ED LOAD AND CURRENT METERS.NOTETWO OR MORE GENERATOR SETS CAN BE OPERATED IN PARALLEL.PARALLELING PROCEDURES-ARE THE SAME AS THOSE DESCRIBEDABOVE.ONE GENERATOR AT A TIME IS BROUGHT ON LINE.CAUTIONPRIOR TO REMOVAL OF GENERATOR SETS FROM PARALLEL OPERATION,MAKE SURE THE LOAD DOES NOT EXCEED THE FULL LOAD RATING OFGENERATOR SETS(S) REMAINING ON LINE.REMOVE A GENERATOR SET FROM PARALLEL OPERATION, PLACE THE CIRCUITBREAKER SWITCH OF THE SET IN THE OPENPOSITION.STOP THE SET AS DESCRIBED IN FIGURE2-8.B - PARALLEL OPERATION (LOAD TRANSFER)THE FOLLOWING METHOD OF PARALLEL OPERATION IS TO BE USED WHEN IT IS NECESSARY TOTRANSFER THE LOAD FROM ONE SET TO THE OTHER WITHOUT INTERRUPTING POWER.Figure 2-10. Parallel Operation (Load Sharing and Load Transfer) (Sheet 3 of 5)Change 122-26.1
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business