Figure 3-51,. Generator and regulator testing.
Figure 3-56. Slave receptacles, removal and installation

Generator Set, Diesel Engine: 200 Kw, 60 Cycle, Ac, 120/208V, 240/416V, 3 Phase. Convertible Fo 167 Kw, 50 Cycle 120/208V, 240/416V, 3 Phase Page Navigation
  79    80    81    82    83  84  85    86    87    88    89  
img
. .
TM 5-6115-400-12
Figure 3-53. Generator regulator, removal and
installation.
Figure 3-54. Overspeed governor, removal and
3-59. Overspeed Governor
installation.
Removal and Installation. Refer to figure 3-54 and
remove the overspeed governor.
3-60. Engine Shut-Down Switches
a. Removal and Installation. Refer to figure 3-55
and remove the low oil pressure and high water
temperature shutdown switches.
b. Switch Settings.
(1) The low oil pressure shut-down switch is set to
open at 15 psi and to close at 25 psi.
(2) The high water temperature switch is set to
open at 217F.  3F, and to close at 205
3F.
3-61. Slave Receptacle
Figure 3-55 (1). Engine shutdown switches, removal
Removal and Installation. Refer to figure 3-56 and
and installation.
remove the slave receptacle.
3-57