TM 5-6115-400-12
(1) DETERMINE THAT BATTERY IS FULLY
ABOVE. IF BATTERY VOLTAGE (24 VOLTS)
CHARGED AND THAT ALL BATTERY AND
IS NOT INDICATED, THE STARTER IS
STARTER CABLES ARE SERVCEABLE AND
DEFECTIVE AND MUST BE REPLACED.
PROPERLY INSTALLED.
(5) MOMENTARILY CONNECT A JUMPER AS
(2) REMOVE
SOLENOID-TO-STARTER
READING SHOULD DROP TO ZERO AND
STARTER SHOULD CRANK ENGINE. IF
AS SHOWN IN B ABOVE. IF VOLTAGE IS
VOLTMETER READING DOES NOT DROP TO
INDICATED,
SOLENOID
SWITCH
IS
DEFECTIVE AND MUST BE REPLACED.
(3) INSTALL
THE
SOLENOID-TO-STARTER
READING DROPS TO ZERO BUT STARTER
CONNECTOR.
FAILS TO CRANK ENGINE, STARTER IS
DEFECTIVE AND MUST BE REPLACED.
6115-400-12/3-49
Figure 3-49. Starting motor and solenoid switch testing.
is increased, stop the engine and connect
regulator. Refer to sub-paragraph (5) above
a jumper wire between armature and field
terminals.
If charging rate does not
to polarize generator. Failure to polarize
increase as engine speed is increased,
generator may cause regulator contacts to
be damaged by vibration, heavy arching,
adjusted or replaced.
and burning.
Caution: Generator must be polarized
whenever leads to generator or generator
remove generator.
regulator have been removed or any
3-55