TM 9-6115-668-13
9.
Remove five nuts (23), five screws (27), five serrated lock washers (24), five washers (25), five screws (27), and
five washers (26) from partition (20) and remove plate (21).
10.
Remove knurled nut (32) and remove plug connector (33) of pick-up cable (7).
11.
Pull pick-up cable (7) through opening in partition (20).
1.
Install pick-up (7) through opening in partition (20) and place plug connector (33) on pick-up (31).
2.
Install five screws (27). five washers (28) into partition (20) and set plate (21) on screws (27).
3.
Install five serrated lock washers (24), five washers (25), five screws (27) and five nuts (23). Tighten nuts (23).
4. Slide PG union onto pick-up cable (7) and tighten.
5.
Slide pick-up cable (7) with PG union through back panel 01 control cabinet (3) and install locknut (6).
6.
Noting correct labeling and position, lay pick-up cable (7) in cable conduits (12 to 14) and connect to terminal strip
(11).
7. Install cables (7) on terminal strip (11).
8.
Close cable conduits (12 to 14) and swing digital isochronous load sharing module N4 (15) back into place.
NOTE
Hold standoffs (19) while installing nuts (16).
9.
Install two washers (18), two serrated lock washers (17), and two nuts (16). lighten nuts (16).
10. Stow prop (5) and close front panel (4).
11.
Install unit hood assembly (1) as instructed in paragraph 4.14.
12. Connect load bank to generator set and perform procedures in paragraph 5.53.
5-206
Change 1