TM 9-6115-668-13
1.
2.
3.
4.
5.
6.
7.
8.
9.
Install actuator cable (9) through opening in partition (20) of base frame (22) and place plug connector (37) on
actuator assembly (38).
Install two screws (34) two serrated lock washers (35) and two washers (36) on plug connector (37).
Install five screws (27), five washers (26) on partition (20) and install plate (21) using five serrated lock washers
(24), five washers (25), five screws (27) and five nuts (23). Tighten nuts (23).
Slide PG union onto actuator cable (9) and tighten.
Slide actuator cables (9) with PG union through back panel of control cabinet (3) and install locknut (8).
Noting correct labeling and position, lay actuator cable (9) in cable conduits (12 to 14) and connect to terminal
strip (11).
Close cable conduits (12 to 14) and swing digital isochronous load sharing module N4 (15) back into place.
NOTE
Hold standoffs (19) while Installing nuts (16).
10.
11.
Install two washers (18) and two serrated lock washers (17) and two nuts (16).
Stow prop (5) and close front panel (4).
Install unit hood assembly (1) as instructed in paragraph 4.14.
Connect load bank to generator set and perform procedures in paragraph 5.53.
5-202
Change 1