TM 9-6115-668-13
2.
Set time relay K107 (6) to switching time time1 = 108 seconds and time 2 = 60 seconds:
a. Set switching time time1:
On front of time relay K 107 (6), use TIME DIP switches (1) to set a time window of 3 minutes as
shown in figure 5-34.
On front of time relay K 107 (6), use rotary knob (3) to set a multiplication factor of .6.
b. Set switching time time2:
On front of time relay K 107 (6), use TIME DIP switches (1) to set a time window of 1 minutes as
shownin figure 5-34.
On front of time relay K 107 (6), use rotary knob (3) to set a multiplication factor of 1.
Figure 5-34 Time Relay K107
3.
Set time relay K108 (7) to switching time on 700 seconds:
a. On front of time relay K 108 (7), set FUNCTION DIP switches (1) as shown in figure 5-35.
b. On front of time relay K 108 (7), use TIME DIP switches (3) to set a time window of 30 minutes
as shown in Figure 5-35.
c. On front of time relay K 108 (7), use rotary knob (5) to set a multiplication factor of .4.
5-148