TM 9-6115-668-135.20 TIME RELAY MAINTENANCE.This task covers:a. Removalb. Testc. Installationd. AdjustINITIALSETUPToolsEquipment ConditionsGeneral Mechanic’s Tool Kit(item 2, appendix B)Automotive Fuel and Electrical System Repair, Tool Kit(item 3, appendix B)Watch, stop(item 5, appendix B)Materials/PartsReferenceGenerator Set 150 kW shut down,paragraph 2.5.2Cable ties(item 10, appendix E)WARNINGDisconnect the negative battery cable first and then the positive bat-tery terminal cables. Failure to observe this warning could result in se-vere personal injury or death.C A U T I O NTag all cables prior to removal to ensure correct connection of the cablesduring installation.REMOVAL1.Open flap (2, figure 5-37) on unit hood assembly (1).2.Open front panel (4) of control cabinet assembly (3) and secure with prop (5).N O T ERemoval procedure for all time relays is the same as for time relayK106, described below.3.Record labeling and position of cables (23, 25) to upper terminals (22, 26) of time relay K106 (27),loosen screws (21, 24) and remove cables (23, 25).4.Record labeling and position of cables (31, 34) to lower terminals (32, 35) of time relay K106 (27),loosen screws (33, 36) and remove cables (31, 34).5.Use a screwdriver to push locking element (30) on time relay K106 (27) in direction of arrow, tilttime relay K106 (27) upward, and remove from mounting bar (41).5 - 1 4 5