TM 9-6115-668-13
4.75 BATTERY CHARGING ALTERNATOR REGULATOR N6 MAINTENANCE.
This task covers:
a. Removal
b. Installation
Equipment Conditions
General Mechanics Tool Kit
(item 2, appendix B)
Automotive Fuel and Electrical System Repair, Tool Kit
(item 3, appendix B)
Reference
Generator Set 150 kW shut
down,
paragraph 2.5.2
WARNING
Disconnect the negative battery cable first and then the positive bat-
tery terminal cables. Failure to observe this warning could result In se-
vere personal injury or death.
CAUTION
Tag ail cables prior to removal to ensure correct connection of the cables
during installation.
1.
Open flap (3, figure 4-60) on unit hood assembly (1).
2.
Remove cable with plug connector 2J5 (45) from battery charging alternator regulator N6 (46).
3.
Remove two nuts (49), two serrated lock washers (48), two washers (47), two screws (43), and two
washers (44) and remove battery charging alternator generator regulator N6 (46) from bracket (60).
1.
Install battery charging alternator generator regulator N6 (46) on bracket (60), using two screws
(43) two washers (44), two washers (47), two serrated lock washers (48), and two nuts (49).
Tighten nuts (49).
2.
Install plug connector 2J5 (45) on battery charging alternator generator regulator N6 (46).
3. Close flap (3).
4-184