TM 9-6115-659-13&PTable 2-2. Operator Preventive Maintenance Checks and ServicesLocationItemIntervalProcedureNot Fully MissionNo.Item to Capable if:Check/Service42DuringCONTROLS AND Observe the following indicators andFrequency or ACINDICATORSensure they are operating properly.voltmeterinoperative.COOLANT TEMP.170-200°F (77-930C)OIL PRESSURE 25-60 psi (172-414 -kPa)FREQUENCY60 HzVOLTAGE120-240 VAC43DuringGROUND RODInspect ground rod and cable for looseCable is missing orCABLE ANDconnections, breaks, damage anddamaged.CONNECTIONScorrosion.44AfterHOUSINGa. Check doors, panels, hinges, andCannot secureclamping catches for damaged, loose, ordoors.corroded items.b. Inspect air intake and exhaust grills fordebris.45AfterIDENTIFICATION Check to ensure identification plates arePLATESsecure.46AfterSKID BASEInspect skid base for cracks and corrosion.Skid base iscracked or showssigns of structuraldamage.47AfterENGINECheck for loose, damaged, or missingASSEMBLYhardware.48AfterFUEL SYSTEMInspect fuel system for leaks, andAny fuel leaks, anddamaged, loose, or missing hardware.damaged, loose, ormissing parts.49AfterFUEL FILTER/a. Inspect fuel filter/water separator forAny fuel leaks.WATERleaks, cracks, damage, properSEPARATORmounting, or missing parts.b. Drain water from fuel filter/waterseparator.WARNINGThe fuels used in this generator set are highly explosive. Do not smoke or use open flamewhen performing maintenance. Flames and explosion can occur resulting in severepersonal injury or death.2-26 Change 2
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business