Pull rear leveling-support jack (2) down. Insert pin (1) in bracket (3) to secure rear leveling-
support jack (2) in down position.
Turn leg base (4) until it makes firm contact with ground.
2-3.2.2 External Fuel Line Connection. Each generator set has provisions for obtaining fuel from an
external source, such as a 5-gallon fuel can or a 55-gallon diesel fuel container. This enables operation for
long intervals without frequent refilling of the fiel tank. To use an external fiel source
WARNING
The fuel in this generator set is highly explosive. Do not smoke or use open
flame when performing maintenance. Flames and explosion could result in
severe personal injury or death.
a. Place the external fiel source (2, figure 2-6) several feet, but no more than 25 feet, away from
the generator set.
Figure 2-6. Auxiliary fuel (Typical).
2-30