TM 9-6115-659-13&P
Table 2-2. Operator Preventive Maintenance Checks and Services
Location
Item
Interval
Procedure
Not Fully Mission
No.
Item to
Capable if:
Check/Service
WARNING
Battery acid can cause burns to unprotected skin.
WARNING
Batteries give off a flammable gas. Do not smoke or use open flame when performing
maintenance. Flames and explosion could result in severe personal injury or death.
30
Before
BATTERY
Inspect cables and connectors for
Cables are loose,
CABLES
corrosion, damage, loose, or missing parts.
damaged, or
missing.
WARNING
High voltage is produced when this generator set is in operation. Personal injury or death
due to electrocution could result.
31
Before
OUTPUT BOX
a. Check for loose or damaged wiring or
Loose or damaged
ASSEMBLY
cables.
wiring or cables.
b. Check output terminals for damage or
Damaged or
missing hardware.
missing hardware.
32
Before
CONTROLS AND
a. Check all indicators and controls for
Indicators or
INDICATORS
damage or missing parts.
controls damaged
or missing.
b. Press PUSH TEST RESET LAMPS
button (46) on fault indicator. All
lights must light.
Change 2 2-23