TM 9-6115-604-34
NAVFAC P-8-633-34
Table 1-5. System Capacities and Detailed Data on Components (Continued)
AC ELECTRICAL POWER GENERATION AND CONTROL SYSTEM (CONTINUED)
Manufacturer:
Part Number:
Model Number:
FSCM:
Load Circuit Breaker Assembly
Drawing Number:
Mechanical Characteristics:
Trip Coil:
Closing Coil:
Manual Operation:
Operating Temperature:
Storage Temperature:
Humidity Conditions:
Manufacturer:
Part Number:
FSCM:
Surge Capacitor
Drawing Number:
Number of Poles:
Voltage Rating:
Operating Temperature:
Storage Temperature:
Humidity Conditions:
Manufacturer:
Part Number:
FSCM:
Power Relay
Drawing Number:
Contacts:
Coil Input:
Terminals:
Rating:
Coil Data:
Coil Resistance:
Current:
Voltage:
Electrical Life:
Basler Electric Company
9059700-106
SR8F3
97520
80-7458
Circuit breaker per NEMA SG-4,
vacuum draw out type, vacuum rated
1200 amperes continuous, 4.16 kV
and 250 mA interrupting
24 V dc nominal (18 to 30 V), 30 amperes maximum
120 V ac, 50/60 Hz, 6 amperes maximum
Via operating (crank) handle furnished for closing,
tripping, charging, and drawing out circuit breaker
-25 to +125F (-31 to 51C)
-65° to +155F (-53 to 68C)
To 100%
Howe-Yin, Inc.
HVDS-0525-01
05464
80-7413
3
4800 V ac
-25 to +125 F (-31 to 51 C)
-65° to +155 F (-53 to 68 C)
To 100%
Westinghouse
1 N02180A01
89946
80-7845
SPDT 0.312 dia silver
50/60 Hz
Screw type
120 V ac, 25 amperes at 277 V ac, 1 hp at 120/240 V ac
DC resistance - 290 ohms 15% at 77 F (25C)
63,800 ohms maximum with suppression
85 milliamperes
600 V ac maximum
10, 000 operation at rated load 77F (25C)
1-24