TM 9-6115-604-34
NAVFAC P-8-633-34
Table 1-5. System Capacities and Detailed Data on Components (Continued)
AC ELECTRICAL POWER GENERATION AND CONTROL SYSTEM (CONTINUED)
Contact Snap Action Switch:
Operation:
Power:
Duty:
Operating Temperature:
Storage Temperature:
Humidity Conditions:
Initial Insulation Resistance:
Insulating Material:
Initial Breakdown Voltage:
Manufacturer:
Part Number:
FSCM:
Time Delay Relay
Drawing Number:
Operating Voltage:
Timing Ranges:
Repeat Accuracy:
Temperature Variation:
Voltage Variation:
Overall Accuracy:
Output DPDT:
Temperature Range:
Storage Temperature:
Mounting/Terminals:
Mechanical Life:
Transient Duration:
Current Drain at 24 V dc
and 68F (20C):
Dielectric:
Manufacturer:
Part Number:
FSCM:
Rated at 77F (25C) 5 amperes at #120 V ac, 60 Hz
AC-85% of nominal voltage at 77F (25C)
9.8 volt amperes at 77F (25C)
Continuous
-25 to +125F (-31 to 51C)
-65 to +155F (-53 to 68C)
To 100%
100 megohms minimum
Molded phenolic
2000 volts rms between all elements and ground
(minimum)
Potter and Brumfield
PRD5AY01 20V
77342
80-7842
24Vdc+10 to 15%Vdc
16.7 K 10% ohms/sec; 2 to 60 minutes calibrated
within +10% to #-1 % of value at 68 F (20C)
1%
5%
±0.25%
±5.25%
10 amperes resistive rating
-22 to 149F (-30 to 65C)
-40 to 185F (-40 to 85C)
Nylon case with 8-pin phenolic base
50 million cycles
Less than 0.1 millisecond 1000 volts at 24 V dc; less
than 1 millisecond 240 volts at 24 V dc
75 milliamperes
1000 V ac between terminals and case, and between
mutually isolated contacts
Agastat
SSC1201A
90403
1-25