TM 9-6115-604-34NAVFAC P-8-633-34Table 1-5. System Capacities and Detailed Data on Components (Continued)AC ELECTRICAL POWER GENERATION AND CONTROL SYSTEMSwitchgear Circuit BreakerDrawing Number:Voltage Rating:Number of Poles:Current Rating:Operating Temperature:Storage Temperature:Humidity Conditions:Specifications:Interrupting Capacity:Wire Size:Manufacturer:Part Number:FSCM:GeneratorDrawing Number:Specifications:Mechanical Characteristics:Weight:Phase:Frequency:Poles:Speed:Duty:Overload:Temperature Rise:Ambient Temperature:Enclosure:Efficiency:Rating:Power Factor:80-7365120/140 V ac215 amperes-25 to +125F (-31° to 51C)-65° to +155F (-53° to 68C)To 100%Per Federal Specification WC-375/6UL listed10,000 amperesNo. 1 to 300 mcmGeneral Electric CompanyTHQEZ1 1 5WL2843280-7543MIL-G-82058C, ANSI C50.10, ANSI C50.12,NEMA MG1Synchronous rotating field,brushless, air-cooled, self-ventilated5700 pounds (2590 kg)350/60 Hz41500/1800 rpmContinuous2 hour overload at 100% of the 60 Hz rating from -25to 125F (-31° to 51C) and at altitudes from sealevel to 1500 feet (457 m)95 degrees by resistance-21.5° to +125F (-29 to 51C)Open drip proof94.4%62.5/750 kW0.8 lagging1-22