TM 9-6115-604-34
NAVFAC P-8-633-34
Table 1-5. System Capacities and Detailed Data on Components (Continued)
AC ELECTRICAL POWER GENERATION AND CONTROL SYSTEM
Switchgear Circuit Breaker
Drawing Number:
Voltage Rating:
Number of Poles:
Current Rating:
Operating Temperature:
Storage Temperature:
Humidity Conditions:
Specifications:
Interrupting Capacity:
Wire Size:
Manufacturer:
Part Number:
FSCM:
Generator
Drawing Number:
Specifications:
Mechanical Characteristics:
Weight:
Phase:
Frequency:
Poles:
Speed:
Duty:
Overload:
Temperature Rise:
Ambient Temperature:
Enclosure:
Efficiency:
Rating:
Power Factor:
80-7365
120/140 V ac
2
15 amperes
-25 to +125F (-31° to 51C)
-65° to +155F (-53° to 68C)
To 100%
Per Federal Specification WC-375/6
UL listed
10,000 amperes
No. 1 to 300 mcm
General Electric Company
THQEZ1 1 5WL
28432
80-7543
MIL-G-82058C, ANSI C50.10, ANSI C50.12,
NEMA MG1
Synchronous rotating field,
brushless, air-cooled, self-ventilated
5700 pounds (2590 kg)
3
50/60 Hz
4
1500/1800 rpm
Continuous
2 hour overload at 100% of the 60 Hz rating from -25
to 125F (-31° to 51C) and at altitudes from sea
level to 1500 feet (457 m)
95 degrees by resistance
-21.5° to +125F (-29 to 51C)
Open drip proof
94.4%
62.5/750 kW
0.8 lagging
1-22