TM 9-6115-604-34
NAVFAC P-8-633-34
Table 1-5. System Capacities and Detailed Data on Components (Continued)
AC ELECTRICAL POWER GENERATION AND CONTROL SYSTEM (CONTINUED)
Output Voltage:
Manufacturer:
Part Number:
FSCM:
Voltage Regulator
Drawing Number:
Sensing Terminals (El, E2 and E3):
Voltage:
Burden:
Input Power (Terminals 3 and 4):
Voltage:
VA (maximum continuous):
Output Field Power
(Terminals F+ and F-):
Maximum Continuous:
Maximum Forcing:
DC Field Resistance (minimum):
Frequency:
Voltage Regulation:
Response Time:
EMI (Electromagnetic
Interference):
Voltage Adjust Range:
Ambient Operating Temperature:
Storage Temperature:
Temperature Coefficient:
Power Dissipation:
Vibration:
With operating voltage selector in 2400 volt connection
position:
A. At 60 Hz: 2160 to 2640 volts
B. At 50 Hz: 1980 to 2420 volts
With operating voltage selector in
2400/4160 volt connection position:
A. At 60 Hz: 3750 to 4575 volts
B. At 50 Hz: 3420 to 4180 volts
Marathon Electric
SS511352
38151
80-7546
120/203/240/416/430/600 V ac
Less than 10 VA per line
240 V ac
1680
125Vdcat7A
180 V dc at 1OA
18 ohms
50/60 Hz
Less than 1.4%
Less than 17 milliseconds
MIL-STD-461, Class III B,
conducted or radiated
10% of nominal voltage
-67 to 158° F (-55 to +70C)
-85 to 212 F (-65 to +10C)
Less than ±1.2% for 122 F (50C)
temperature change (after 20 minutes
warm-up)
Less than 60 watts
Withstands 1.3 G's from 5 to 26 Hz, 0.036 inch
displacement from 26 to 52 Hz and 5 G's from
52 to 260 Hz
1-23