ARMY TM 9-6115-604-12
NAVY NAVFC P-8-633-12
Table 2-2. Generator Control Panel B, Controls and Instruments (Continued)
Figure 2-2, 5
SYNCHROSCOPE M106
Used with SYNCHRONIZING LIGHTS
--
DS110 and DS111 when paralleling.
When the SYNCHROSCOPE pointer is
at the 12 o'clock position, DS110 and
DS111 will be dark. Shows phase rela-
tionship between on-line and incoming
units.
Figure 2-2, 6
AC KILOWATTS meter M107
Indicates kilowatt output of generator
50 Hz - 625
set.
60 Hz - 750
Figure 2-2, 7
AC KILOVARS meter M108
Indicates kilovar output of generator set.
50 Hz - 469
60 Hz - 562
Figure 2-2, 8
FREQ ADJ rheostat R102
Provides adjustments of generator set
--
frequency In single set operation or load
in parallel operation
Figure 2-2, 9
POWER FACTOR meter M104
Indicates power factor of generator set
50 Hz - 0.8
output. LAG Indicates an Inductive load.
60 Hz - 0.8
LEAD indicates a capacitive load.
Figure 2-2, 10
GEN TEMP meter M105
Indicates temperature of generator G1
Normal ambient
windings at selected points
to 150
F (66
C)
Figure 2-2, 11
SYNCHROSCOPE switch S115. Used to turn SYNCHROSCOPE M106
OFF.
ON or OFF.
Figure 2-2, 12
FREQUENCY DROOP/ ISO-
Used to select ISOCHRONOUS or
CHRONOUS switch S117
FREQUENCY DROOP paralleling
Figure 2-2, 13
TEMPERATURE INDICATOR
Used with GEN TEMP meter M105 to
--
switch S113
read generator G1 temperature at one
of the six equally spaced points around
the stator.
Figure 2-2, 14
Phase sequence lights (1-2-3,
Used with PHASE SEQ SEL. SW S119
Dark
3-2-1) DS112 and DS113
to compare generator and bus phase
sequence.
Figure 2-2, 15
PHASE SEQ. SEL. SW S119
When set to GEN or BUS, indicates
Both GEN and
whether phase is 1-2-3 or 3-2-1.
BUS should indi-
cate same phase
sequence.
Figure 2-2, 16
PHASE SEQ LAMP TEST
Used to test phase sequence lights
When button is
pushbutton S116
DS112 and DS113.
pressed, DS112
and DS113
should light.
Figure 2-2, 17
PARALLEL Indicator DS35 and Indicates setting of PARALLEL Switch
SINGLE SET indicator DS36
S6.
Figure 2-2, 18
PARALLEL switch S6
Used to select PARALLEL or SINGLE
set operation.
Figure 2-2, 19
OPEN indicator DS33 and
Indicates whether load circuit breaker
CLOSED indi-
CLOSED indicator DS34
CB101 Is OPEN or CLOSED.
cator DS34 lit,
OPEN indicator
DS33 dark.
FIGURE
AND
INDEX NO.
CONTROL OR
INSTRUMENT
FUNCTION
NORMAL
READING/
SETTING AT
RATED LOAD
2-6