ARMY TM 9-6115-604-12
NAVY NAVFC P-8-633-12
Table 2-1. Engine Control Panel C, Controls and Instruments
Figure 2-1, 1
MAINTENANCE LOCKOUT
When set to LOCKOUT, disconnects
OPERATE
switch S100
battery power from DC control circuits
Figure 2-1, 2
24 V DC CONTROL POWER
When set to ON, DC control circuits
ON
CIRCUIT BREAKER CB1
are operable CB1 will automatically
open If control circuit current exceeds
20 amperes
Figure 2-1, 3
EMERGENCY SHUTDOWN
If pressed while operating, EMER-
--
push-button S7
GENCY SHUTDOWN pushbutton S7
will stop the engine by cutting off air to
the turbochargers and de- energize
fuel solenoid valve.
Figure 2-1, 4
FUEL PUMP switch S8
When set to AUTO, the fuel transfer
AUTO
system will fill the fuel tank (from an
external source) when the fuel level
becomes low When set to HAND, the
fuel transfer system will short cycle on
and off When set to OFF, the fuel
transfer system will not operate
Figure 2-1, 5
FUEL PUMP ENERGIZED
Lights to indicate fuel transfer Indicator
Dark
Indicator DS107
pump motor 8103 Is operating.
Figure 2-1, 6
Panel Lights DS26, DS27,
Illuminate engine control panel C.
Dark
DS28, and DS29
Figure 2-1, 7
LUBE OIL PRESSURE gage
Indicates engine oil pressure.
60 to 90 psi
M1
(413.7 to 620.6
kPa)
Figure 2-1, 8
FUEL LEVEL gage M4
Indicates fuel tank level.
Greater than
empty
Figure 2-1, 9
EXHAUST TEMP gage M6
Indicates exhaust temperature at
800 to 1000°F
turbocharger outlets
(427 to 5380C)
Figure 2-1, 10
COOLANT TEMP gage M3
Indicates engine water temperature at
180 to 200°F
the thermostats
(82 to 930C)
Figure 2-1, 11
LUBE OIL TEMP gage M2
Indicates engine oil temperature
180 to 230°F
(82 to 110°C)
Figure 2-1, 12
TIME TOTALIZING meter M5
Indicates how many hours the genera-
--
tor set has run.
Figure 2-1, 13
PANEL LIGHTS switch S1
When set to ON, panel lights DS26 to
OFF
DS29 illuminate.
Figure 2-1, 14
START AID switch S10
When set to ON and released, a me-
OFF
tered amount of ether is Injected into
the engine intake No ether is injected
until switch is released
FIGURE
AND
INDEX NO.
CONTROL OR
INSTRUMENT
FUNCTION
NORMAL
READING/
SETTING AT
RATED LOAD
2-3