ARMY TM 9-6115-604-12
NAVY NAVFC P-8-633-12
Table 2-2. Generator Control Panel B, Controls and Instruments (Continued)
Figure 2-2, 20
BREAKER CONTROL switch
Used to open and close load circuit
--
S4
breaker CB101.
Figure 2-2, 21
OPERATION SELECTOR
When set to MANUAL, the generator set
--
SWITCH S3
must be manually operated from the
control room or remote control module.
When set to AUTO, the generator set is
controlled by the site requirement
module
Figure 2-2, 22
TEL JACK J15
Allows for voice communication, via
--
headsets, between the control room and
the engine compartment or RCM
Figure 2-2, 23
LOCAL REMOTE switch S2
When set to LOCAL, the generator set
--
is operable from the control room When
set to REMOTE, the remote control
module Is used to operate the set.
Figure 2-2, 24
GEN/BUS VOLTMETER switch
Used with AC KILOVOLTS meter M101
--
S112
to read generator set or bus line voltage.
Figure 2-2, 25
AMMETER SWITCH S114
Used with AC AMPERES meter M102 to
--
read current output of a selected phase
Figure 2-2, 26
VOLT ADJUST rheostat R101
Allows adjustment of generator set volt-
--
age output
FIGURE
AND
INDEX NO.
CONTROL OR
INSTRUMENT
FUNCTION
NORMAL
READING/
SETTING AT
RATED LOAD
2-7