ARMY TM 9-6115-604-12NAVY NAVFC P-8-633-12Figure 2-2. Generator Control Panel B, Controls and InstrumentsTable 2-2. Generator Control Panel B, Controls and InstrumentsFigure 2-2, 1AC AMPERES meter M102Indicates load current on a selected50 Hz - 119phase60 Hz - 130 Va-ries with load.Figure 2-2, 2AC KILOVOLTS meter M101Indicates voltage between selected50 Hz - 3800lines60 Hz - 4160Figure 2-2, 3FREQUENCY meter M103Indicates frequency of generator set output.50 or 60Figure 2-2, 4SYNCHRONIZING LIGHTSUsed when paralleling to bring an in-Both lights darkDS110 and DS111coming set on-line in phaseFIGUREANDINDEX NO.CONTROL ORINSTRUMENTFUNCTIONNORMALREADING/SETTING ATRATED LOAD2-5
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business