ARMY TM 9-6115-604-12
NAVY NAVFC P-8-633-12
Table 2-4. Annunciator Panel A9 Indicators (Continued)
Figure 2-4, 3
LOW LUBE OIL PRESSURE in- Indicates that oil pressure shutdown
Dark
dicator A9DS2
switch OP2 has sensed an engine oil
pressure of 37 to 41 psi (267 to 271
KPa) or lower
Figure 2-4, 4
Spare Indicator A9DS12
To allow for the future addition of a new
Dark
alarm circuit or to be used as a spare if
an alarm circuit fails.
Figure 2-4, 5
OVERSPEED indicator A9DS1
Indicates that overspeed switch SS3
Dark
has sensed an engine speed greater
than 2200 rpm.
Figure 2-4, 6
EXCESSIVE CRANKING Indi-
Indicates that crank cycle timer M7 has
Dark
cator A9DS13
put the generator set through fourconse-
cutive start cycles but the engine failed
to start.
Figure 2-4, 7
HIGH FUEL LEVEL indicator
Indicates that high fuel level switch FL4
Dark
A9DS6
has sensed a high fuel condition in the
generator set fuel tank
Figure 2-4, 8
OVERVOLTAGE indicator
Indicates that overvoltage relay K110
Dark
A9DS7
has sensed that line-to-line voltage of
generator G1 line T1, T2, and/or T3 has
risen to 4730 f 100 V ac, or higher, for 3
1 seconds.
Figure 2-4, 9
REVERSE POWER Indicator
Indicates that reverse power relay K109
Dark
A9DS10
has sensed that generator G1 has been
motonng (receiving current instead of
delivering current)
Figure 24, 10
UNDERVOLTAGE indicator
Indicates that undervoltage relay Kill
Dark
A9DS8
has sensed that line-to-line voltage of
generator G1 line T1, T2, and/or T3 has
fallen below 3540 V ac for more than 1.5
1 seconds
Figure 2-4, i1
LOW COOLANT LEVEL indica- Indicates that coolant level warning
Dark
tor A9DS1 5
switch S13 has sensed an unacceptably
low level of coolant in the radiator.
Figure 24, 12
UNDER FREQUENCY indicator Indicates that under frequency relay
Dark
A9DS14
K107 (60 hertz operation) or K108 (50
hertz operation) has sensed abnormally
low frequency output from generator G1.
Figure 2-4, 13
Spare indicator A9DS16
To allow for the future addition of a new
Dark
alarm circuit or to be used as a spare if
an alarm circuit fails
Figure 2-4, 14
Spare indicator A9DS17
To allow for the future addition of a new
Dark
alarm circuit or to be used as a spare If
an alarm circuit fails
FIGURE
AND
INDEX NO.
CONTROL OR
INSTRUMENT
FUNCTION
NORMAL
READING/
SETTING AT
RATED LOAD
2-11