ARMY TM 9-6115-604-12NAVY NAVFC P-8-633-12Table 2-6. Load Sharing Panel A104, ControlsFigure 2-6, 1GAINTo adjust sensitivity of governor to a--change In load. Clockwise adjustmentincreases gain. Instability will result withfull clockwise adjustment. Full counter-clockwise adjustment will result in slug-gish control.Figure 2-6, 2STABILITYTo adjust the governor time constant--Time constant is length of time requiredfor engine to return to set speed afterchange In load Clockwise adjustmentshortens the time constantFigure 2-6, 3FREQUENCY ADJUSTTo adjust engine speed on initial factory--setup Clockwise adjustment increasesthe speed setting. Normal frequency ad-just rheostat on cabinet B control panel.Figure 2-6, 4DROOPTo adjust frequency droop for parallel or--single unit operation.Figure 2-6, 5LOAD SHARING SENSITIVITY To adjust paralleling cable signal when--paralleling with other, identical generatorsets.Figure 2-6, 6LOAD ANTIC ADJUSTTo adjust governor response under load--applicationFigure 2-6, 760 CYCTo provide coarse adjustment of fre---quency for 60 Hz operationFigure 2-6, 850 CYCTo provide coarse adjustment of fre---quency for 50 Hz operationFIGUREANDINDEX NO.CONTROL ORINSTRUMENTFUNCTIONNORMALREADING/SETTING ATRATED LOAD2-16