Table 2-6. Load Sharing Panel A104, Controls
Figure 2-6, 1
GAIN
To adjust sensitivity of governor to a
--
change In load. Clockwise adjustment
increases gain. Instability will result with
full clockwise adjustment. Full counter-
clockwise adjustment will result in slug-
gish control.
Figure 2-6, 2
STABILITY
To adjust the governor time constant
--
Time constant is length of time required
for engine to return to set speed after
change In load Clockwise adjustment
shortens the time constant
Figure 2-6, 3
FREQUENCY ADJUST
To adjust engine speed on initial factory
--
setup Clockwise adjustment increases
the speed setting. Normal frequency ad-
just rheostat on cabinet B control panel.
Figure 2-6, 4
DROOP
To adjust frequency droop for parallel or
--
single unit operation.
Figure 2-6, 5
LOAD SHARING SENSITIVITY To adjust paralleling cable signal when
--
paralleling with other, identical generator
sets.
Figure 2-6, 6
LOAD ANTIC ADJUST
To adjust governor response under load
--
application
Figure 2-6, 7
60 CYC
To provide coarse adjustment of fre-
--
quency for 60 Hz operation
Figure 2-6, 8
50 CYC
To provide coarse adjustment of fre-
--
quency for 50 Hz operation