ARMY TM 9-6115-604-12NAVY NAVFC P-8-633-12Table 2-7. Distribution Panel DP2, ControlsFigure 2-7, 1Coolant and oil heater (LB)To provide power and circuit protectionONcircuit breaker CB117to coolant heater H101 and lube oilheater H113Figure 2-7, 2Coolant heater (RB) circuitTo provide power and circuit protectionONbreaker CB110to coolant heater H102.Figure 2-7, 3Spare circuit breaker CB111To be used as a spare, If requiredOFFFigure 2-7, 4Switchgear heater circuitTo provide power and circuit protectionONbreaker CB113to heaters H105, H106, and H107switchgear.Figure 2-7, 5Spare circuit breaker CB114To be used as a spare, if requiredOFFFigure 2-7, 6Switchgear heater circuit break- To provide power and circuit protectionONer CB112to humidistat S107 and contactor Kl17Figure 2-7, 7Battery charger circuit breakerTo provide power and circuit protectionONCB116to battery charger BC1Figure 2-7, 8Fuel transfer system andTo provide power and circuit protectionONcoolant heater circuit breakerto fuel transfer solenoid L102, fuel trans-CB122fer pump contactor K106, and coolantheater contactor K104Figure 2-7, 9Spare circuit breaker CB119To be used as a spare, if requiredOFFFigure 2-7, 10Fuel transfer pump circuitTo provide power and circuit protection--breaker CB121to fuel transfer pump motor B102Figure 2-7, 11Generator heater to circuitTo provide power and circuit protection--breaker CB120generator heaters H109 and H 1 0.Figure 2-7, 12Control room heaters circuitTo provide power and circuit protectionOFF(ON in coldbreaker CB118to control room heaters H103 and H 104weather)FIGUREANDINDEX NO.CONTROL ORINSTRUMENTFUNCTIONNORMALREADING/SETTING ATRATED LOAD2-18
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business