ARMY TM 9-6115-604-12NAVY NAVFC P-8-633-12Table 2-5. Overcurrent Relay K114 Controls and Instruments (Continued)Figure 2-5, 3Current Pickup Tap for phase CProvides for seven pickup settings which4are marked In CT secondary amperes.When a pin is pulled out, that phaseswitches to the maximum tap settingThe pin may be moved with the relay. Inservice.Figure 2-5, 4TRIP test pushbutton for INSTThis pushbutton, recessed to preventfunctionaccidental operations, will produce a tripsignal and operate the INST target (6,below).Figure 2-5, 5INST dialUsed to select instantaneous pickup set-3tings. The markings around the dial Indi-cate multiples of pickup tap setting Forexample, if the phase A tap is set to 6amperes and the INST dial is set at 8,the INST setting is 6 amperes x 8 = 48amperes and an instantaneous trip willoccur at 48 amperes in phase A of therelay.Figure 2-5, 6INST targetOperates if INST circuit causes a tripDarkFigure 2-5, 7TARGET RESET pushbuttonUsed to reset targets after a trip.--Figure 2-5, 8TIME targetOperates If TIME circuit causes a trip.DarkFigure 2-5, 9TIME vernier adjustAllows for TIME settings between valuesFully counter-marked around TIME dial.clockwiseFigure 2-5, 10TIME dialUsed to select one of 10 time-current10curves.Figure 2-5, 11TRIP test pushbutton for TIMEThis pushbutton, recessed to prevent--functionaccidental operations, will produce a tripsignal and operate the TIME target (8,above)FIGUREANDINDEX NO.CONTROL ORINSTRUMENTFUNCTIONNORMALREADING/SETTING ATRATED LOAD2-14