TM5-6115-634-14&PNAVFAC P-8-647-14&PT0-35C2-3-445-14TM-6115-14&P/15-23.MAINTENANCE OF CURRENT TRANSFORMER ASSEMBLIES (cont)TESTINGTEST TRANSFORMER ASSEMBLIES.a.Test current boost transformeras follows:(1) Use an ohmmeter to testfor 0.19 ohms between A1and A2, B1 and B2, C1 andC2.(2) Apply 7 Vac 60 Hz to sec-ondary winding.Excitercurrent should be 75milliamperes maximum.(3) Replace the transformer iftest steps (1) or (2)above failed.b.Test instrumentation trans-former as follows:(1) Use an ohmmeter to testfor 0.11 ohms betweenterminals A1 and A3, B1and B2, C1 and C2.(2) Apply 10 Vac 60 Hz to sec-ondary winding.Excitercurrent should be 50milliamperes maximum.(3) Replace transformer iftest steps b. (1) or (2)failed.c.Test cross-current compensationtransformer as follows:(1) Use an ohmmeter to testfor 0.3 ohms between ter-minals A1 and A2.(2) Apply 10 Vac 60 Hz tosecondary winding.Exci-ter current should be 50milliamperes maximum.5-39