TM5-6115-593-34NAVFAC P-8-631-34TO-35C2-3-463-2(g) Install annunciator (13) by securingbrackets (12) using screws (10) andnuts (11).(h) Connect wires to terminal boards,then remove wire tags.15-11. FLASHER FC1. The flasher (23, figure 15-3) isplugged into terminal block (22) which is mounted on theplate assembly (30) with two screws (20) and nuts (25).Test the flasher by connecting it in series with a 24V DCpower source and test lamp. The test lamp should flashon and off; otherwise the flasher is defective and shouldbe replaced.15-12. TRANSFORMER T103 (29, figure 15-3).a. Remove phase shift transformer T103 asfollows:(1) Tag and disconnect lead wires.(2) Remove screws (27) and nuts (28) andremove T103 (29).b. Test transformer T103 in accordance withprocedures in paragraph 5-3 b.c. Install T103 as follows:(1) Secure transformer T103 to plate (30)using screws (27) and nuts (28).(2) Connect wires and remove tags.15-13. RESISTOR R30 (14, figure 15-3).a. Remove R30 (14) from terminal block (19) byremoving screws (17).b. Use an ohmmeter to test R30 for resistance of39,000 ohms ±5 percent. Replace R30 ifspecified resistance value is not met.c. Install resistor R30 (14) onto terminal block (19)using screws (17).15-14. DIODE CR36 (15, figure 15-3).a. Disconnect one end of the diode (15) byremoving screw (17).b. Connect an ohmmeter (scale set at Rx100)across the diode, and note reading.c. Reverse ohmmeter leads to the diode, and againnote reading. A good diode will read highresistance one way and low resistance the otherway. A shorted diode will read full scale bothways. An open diode will read infinity (noreading, in either direction.d. Remove shorted or open diode (15) by removingremaining screw (17).e. Reconnect lead of good diode, or install newdiode with screws (17).Section III. MAINTENANCE OF AUTOMATIC CONTROL MODULE15-15. GENERAL. the Automatic Control Module canautomatically control up to four generator sets bymonitoring the utility bus voltage and frequency. Ifvoltage should vary by ±10 percent or frequency shouldvary by ±3 percent the module will start the generators,open the utility breaker and sequentially load generators.The troubleshooting procedure contained in Table 5-5 and5-6 of the Operator and Organizational Maintenancemanual isolates most faults that may occur. Test andadjustment procedures are contained in this section.15-16. UNDER/OVERVOLTAGE DEVICE. There is oneunder/over voltage device. The device is preset for a ±10percent deviation in the 120V AC bus sensing power. Thedevice is adjustable within the range specified in thetabulated data in Chapter 1 of the Operator andOrganizational Maintenance manual. Trip settings aremade by removing protective plastic caps on front of thedevice and turning adjustment screws beneath caps. Aclockwise rotation of adjustment screw will increase trippoint. Figure 15-9 shows component layout of AutomaticControl Module.15-12
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business