Figure 15-9. Automatic Control Module
Figure 15-10. Under/Over Voltage Relay, Test Setup
TM-5-6115-593-34 Generator Set Diesel Engine Driven Tactical Skid Mtd. 600 Kw 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Page Navigation
298
299
300
301
302
303
304
305
306
307
308
TM5-6115-593-34
NAVFAC P-8-631-34
TO-35C2-3-463-2
LEGEND FOR FIGURE 15-9
1. Rivet
33. BR2 fuse
2. Schematic plate
34. BR3 fuse
3. Data plate
35. BR4 fuse
4. Harness assy
36. Unit 1 fuse
5. Nut
37. Unit 2 fuse
6. Washer
38. Unit 3 fuse
7. Relay panel assy
39. Unite 4 fuse
8. Screw
40. MR1 fuse
9. Over
frequency
relay
41. MR2 fuse
10. Under
frequency
relay
42. MR3 fuse
11. Under/overvoltage relay
43. MR4 fuse
12. Time delay relay
44. Nut
13. Time delay relay
45. Screw
14. Relay
46. Fuse holder
15. Relay
47. Plate, "normal Power"
16.
Diode
48. Plate, "return"
17. Time delay relay
49. Plate, "freq. select"
18. Diode pack
50. Plate, "AC-15A"
19. Time delay relay
51. Plate, "BR1-5A"
20. Run relay
52. Plate, "BR2-5A"
21. Terminal block
53. Plate, "BR3-5A"
22. Terminal block
54. Plate, "BR4-5A"
23. Marker strip
55. Plate, "unit 1DC-5A"
24. Marker strip
56. Plate, "unit 2DC-5A"
25. Marker strip
57. Plate, "unit 3DC-5A"
26. Panel
58. Plate, "unit 4DC-5A"
27. Fuse panel assy
59. Plate, "MR1-5A"
28. Panel light
60. Plate, "MR2-5A"
29. Selector switch
61. Plate, "MR3-5A"
30. Toggle switch
62. Plate, "MR4-5A"
31. AC fuse
63. Fuse panel
32. Fuse, BR1
64. Box assy
a. Test. Test the under/over voltage module as
follows:
(1) Under/over voltage
relay
(11, figure 15-9)
(a) Connect the under/over voltage
device as shown in figure 15-10.
(b) Close S1, adjust variac for 110V
AC on AC
voltmeter
.
(c) With ohmmeter connected between
terminals 5 and 7, reduce AC
voltage.
Relay
should trip at 103V
AC at this point, ohmmeter will no
longer show
continuity
.
(d) With
ohmmeter
connected between
terminals 5 and 6 adjust AC voltage
to read 130 volts.
(e) Increase voltage. Relay should trip
at 132V AC.
Ohmmeter
will no
longer show
continuity
.
b. Replacement.
WARNING
REMOVE 120V AC POWER PRIOR TO MOVING AND
REPLACING DEVICE.
15-14