TM 5-6115-584-12
NAVFAC P-8-622-12
TO-35C2-3-456-1
TM-05682C-12
MAINTENANCE OF CONTROL SYSTEM
4-34. DESCRIPTION
Section XII.
AND FUNCTION.
NOTE
All symbols (CB2, S1, etc.) are the same as
used on the wiring diagram, figure 1-7, and
elsewhere throughout the manual.
4-35. DC CONTROL SYSTEM.
Operation of the dc control system is as follows.
Operator controlled dc functions are all contained in
three items mounted on the control panel. These are
the dc circuit breaker (CB2), the master switch (S1),
and the panel light switch (S2) (see figure 4-33).
a. The dc circuit breaker (CB2) controls all dc
power to the unit. When it is de-energized (pulled
out), all dc control circuits are de-energized, except
the battery charging system which is self protected
by fuse (F1). This breaker can be used for emer-
gency stopping of the unit.
b. The master switch (S1) controls all starting and
operating of the set under normal conditions. It is a
five position rotary switch with the extreme position
in either direction being a momentary position. The
five positions control set operates as follows. When
the master switch is placed in position 1, marked
PREHEAT on control panel, a circuit is completed
between terminals 11 and 15 of the master switch,
this applies power to the coil of the preheat relay
(K2). When the preheat relay contacts close, power is
then applied to the glow plugs and preheater on the
engine. This position of the switch should be used for
starting any time the engine is cold, or has not been
run for sometime. The normal period for preheating
is 1 minute, but can be as long as 1 minute 30 seconds
as conditions dictate. This switch position is momen-
tary so that the preheat circuit remains activated
only as long as the operator holds the switch in
PREHEAT or START position. When the master switch
is placed in position 2, marked OFF on control panel,
all dc circuits are de-energized except the panel
lights, battery indicator, and the battery charging
system. This position is used to stop the set under
normal operation. When the master switch is placed
in position 3, marked PRIME & RUN AUX. FUEL on
control panel, circuits are completed between ter-
minals 11-13, 11-14, 11-17 of the master switch.
This applies power to the engine fuel pumps, and the
auxiliary fuel system and also to one side of an
open contact of relay (K1). This position is used when
the set is running and the auxiliary fuel system is
being used, and also to prime the entire fuel system
before starting. Position 4 of the master switch,
marked PRIME & RUN on the control panel, is the
same as position 3 except that the circuit between
terminals 11-17, of the master switch is not made.
This position is used when the set is running and the
auxiliary fuel system is not being used, and also to
prime the engine fuel system only before starting.
When the master switch is placed in position 5,
marked START on the control panel, circuits are com-
pleted between terminals 11-13, 11-14, 11-15, 25-27,
25-28. The circuits between 11-13, 11-14, 11-15
activate the engine fuel pumps, apply power to one side
of an open contact of relay K1 and activate the pre-
heat circuit as described in previous positions of the
switch. The circuit between 25-28 of the master
switch bypasses the safety devices which are capable
of stopping the engine. Bypassing the low oil pressure
safety device (S5) is essential until the engine has
sufficient oil pressure to close its contacts. By-
passing the safety device completes a circuit to the
engine fuel solenoid and relay coil (K1). Energizing
the start relay (K1) completes a circuit through the
contacts of (K1) to the running time meter, and to
one side of the low oil pressure switch. The circuit
between 25-27 of the master switch applies battery
voltage to the field flash resistor through diode (CR2).
This action applies field flashing current to the
exciter field. It sled applies power through diode
(CR1), which prevents starting set when the battery
polarity is reversed, and the closed contacts of the
start disconnect switch (S7) to the crank relay coil
(K3). When the crank, relay contacts close, a circuit
is completed to the starter solenoid (K6), which
closes and starts the cranking motor. With the
engine fuel solenoid energized and the starting motor
cranking the engine, the engine should start and ac-
celerate toward the speed setting of the governor.
When engine speed passes approximately 1000 RPM
the start disconnect switch contact opens de-ener-
gizing the crank relay (K3) and in turn the start
solenoid and starting motor. With the engine ac-
celerating and ac voltage building up, the governor
will take control of the engine and the voltage regu-
lator will bring voltage to the value set by voltage
adjust rheostat. By the time the Generator Set is
under control of the regulator and governor, the
engine oil pressure will be sufficient to permit re-
turning master switch (S1) to the PRIME & RUN or
PRIME & RUN AUX. FUEL position depending on
desired set operation. The set will now be operating
under control of the voltage regulator and governor
but without any load. As stated above, the set is now
ready to accept a load. Placing the ac circuit breaker
in the ON position connects the selected generator
output to the set load terminals. The breaker can be
opened manually or by automatic action of the internal
relay trip device in the case of an overload or a
short circuit. The panel light switch activates the
panel lights when placed in the ON position.
4-36. AC lNSTRUMENTATION SYSTEM.
Operation of the ac instrumentation system which
consists primarily of ammeter voltmeter and am-
meter-voltmeter transfer switch is as follows. The
function of the ammeter-voltmeter transfer switch
(S8) and the meter switching section of the re-
connection switch (S6) is to provide the connections
4-38