TM 5-6115-584-12NAVFAC P-8-622-12TO-35C2-3-456-1TM-05682C-124-38. CONTROL CUBICLE ASSEMBLY.a. Test, On Equipment (see figure 4-33).NOTEWhen disconnecting leads from terminals, tapeleads to prevent electrical shorts.(1) Control Cubical. Perform operational test on con-trol cubicle, checking for proper operation in each of theGenerator Set’s three modes using a voltmeter of knownaccuracy. Check that ac output voltage indicated on controlpanel matches output voltage at terminal board. Check thatGenerator Set does come to an EMERGENCY STOP whendc control circuit breaker (figure 2-3) is pulled. Test individ-ual components of the control cubicle as given below. Seefigure 4-33 for location of components.(2) With the generator operating at rated speed or 60Hz, flash the generator field by placing the master switch onthe control cubicle in the start position. If the generatorvoltage fails to build up after flashing, the control cubiclemay be defective.(3) Voltage Adjust Reheostat (R1). Turn the Amme-ter Voltmeter transfer switch to its various positions. Foreach position of the switch, turn voltage adjust reheostat toits extreme positions, Voltage readings should be as follows.Voltage adjust range shall be between 205 and 220V for the120/208V, 3 phase, 4 wire connection. Between 114 and126V for the 120V, 1 phase, 2 wire connection. Between 228and 252V for the 120/240V, 1 phase, 3 wire connection.(4) Panel Light Assemblies (DS1) and (DS2). With agood incandescent lamp in place and 24 vdc present at ter-minals of panel light (panel light switch ON) check thatlamps do not light.NOTEBe certain panel light switch is OFF beforeinstalling or replacing panel light assembly.(5) Hour Meter (M2). Operate Generator Set. Checkhour meter against a known accurate time source. Replacemeter if necessary.(6) Battery Charging Indicator (MI), Connect meter capable of reading at least 35 volts DC from terminal onbattery charging indicator to ground. Operate GeneratorSet. With the needle in the yellow area, the meter should readbetween 18 and 27.5 volts. With the needle in the green area,the meter should read between 24.5 and 31.5 volts. NOTE:The apparent overlap in voltage between the yellow high andgreen low is the result of a plus or minus 1.5 voltmetertolerance.(7) DC Control Circuit Breaker (CB2). Operate Gen-erator Set. Pull circuit breaker (CB2). If generator does notcome to an emergency stop, stop the unit using master switchand replace breaker.CAUTIONDisconnect battery cable before making checks,unless otherwise noted.(8) Master Switch (S1). Disconnect battery. Tag anddisconnect seven leads to master switch. Using an ohmme-ter, check for continuity between terminals for each of thefive switch positions as given in table 4-3. If continuity is notfound for each set of terminals listed, replace master switch.(9) Panel Light Switch (S2). Tag and disconnect twoleads to panel light switch. Using an ohmmeter, test forcontinuity between terminals on switch. With the switch inthe OFF position, there should be noTable 4-3 Master Switch Continuity CheckCheck for ContinuitySwitch PositionBetween TerminalsIPREHEATI11-15OFFNONEIRUN AUX FUEL11-13-17RUN11-13START11-13-15 25-27-384-42Change 9
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business