TM 5-6115-584-12NAVFAC P-8-622-12TO-35C2-3-456-1TM-05682C-12Figure 4-34. Removing Control Cubicle Support Assembly(3) Battery Charging Indicator (M1). Tag anddisconnect lead to indicator. Remove two lockwashersand nuts and retainer holding meter in place andremove indicator.(4) DC Control Circuit Breaker (CB2). Discon-nect two leads to breaker. Remove two screwsattaching breaker to control panel and remove breaker.(5) Master Switch (S1). Disconnect battery. Tagand disconnect seven leads to master switch. Re-move switch knob by loosening two setscrews. Removenut attaching switch to control panel and removeswitch.(6) Panel Light Switch (S2). Tag and disconnecttwo leads to switch. Remove nut attaching switchto control panel and remove switch.(7) Ammeter - Voltmeter Transfer Switch (S8). Tagand disconnect sixteen leads to range selector switch.Remove switch knob by loosening two setscrews.Remove nut attaching switch to control panel andremove switch. Install new switch as given above.(8) Voltage Adjust Rheostat (R1). Tag and dis-connect two leads to rheostat. Remove rheostat knobby loosening two allen setscrews. Remove nut andwasher attaching rheostat to panel and remove rheostat(9).(9) Transformer (T1). Tag and disconnect fiveleads to transformer. Remove four screws andlockwashers attaching transformer to control cubicleand remove transformer.(10) Transformer (T2). Tag and disconnect fourleads to transformer. Remove two screws and lock-washers attaching transformer to cubicle and removetransformer.Change 34-43