Figure 423. Battery Charging Alternator
(a) Tag and disconnect stator lead (1) from
stator at terminal block (3) Check between two stator
leads for approximately 0.6 ohms continuity. If open or
shorted, notify higher level of maintenance. Check for
Avoid contact with blower wheel while
continuity between each lead and ground. If continuity
testing battery alternator voltage.
is found, notify higher level of maintenance.
(3) Test.
(b) With the stator leads (1) disconnected,
check voltage across two leads (1) from stator. Voltage
should be in a range of 30-35 volts AC with the engine
operating normally at 1800 RPM, If voltage is less than
30 volts AC, stator on magnets in rotor maybe defec-
tive. Refer to higher level of maintenance for
Do not operate unit more than 3 min-
replacement of stator or rotor. Reconnect stator leads
utes with blower housing removed.
(1).